2020-09-03 17:24:46FOLLOWING COMMENTS FROM RICK ROSSANO, PROJECT
 COORDINATOR, ENGINEERING SERVICES DEPARTMENT,
 561-494-1098, [email protected] :
  
 1. THE CITY OF WEST PALM BEACH HAS A NUMBER OF
 REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY
 AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND
 WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE
 DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK
 BELOW: HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=
 ~\WPB_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION
 -FULL-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC0
 2A97B1960045731D3658206F27451722716EF
 THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE
 FOUND HERE: HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBL
 IC-WORKS/FORMS,-PERMITS-APPLICATIONS
 2. CODE OF ORDINANCES, CITY OF WEST PALM BEACH,
 FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED
 SEPT. 22, 2008. (SUPPLEMENT NO. 18)
 CHAPTER 90 UTILITIES, ARTICLE I. SEC. 90-7.
 POLICY REGARDING EXTENSION OF WATER OR SEWER SERVICE
 FACILITIES OF THE CITY.
 THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
 3. AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
 4. PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1040 FOR FURTHER
 ASSISTANCE.
 5. PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS
 OF ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES,
 INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND
 SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES,
 METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE
 SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING
 GRADES, PIPES SIZES, MATERIALS, ELEVATIONS,
 ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL
 INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER
 LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN
 VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
 PLEASE SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL. ADDITIONALLY, PLAN VIEW SHALL SHOW ALL
 EXISTING AND PROPOSED UNDERGROUND UTILITY LAYOUT,
 INCLUDING FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED ON THE
 RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL
 UTILITY CROSSINGS.
 6. CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 ROW.
 7. PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE
 DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB
 DEVELOPMENT APPLICATION).
 8. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND
 PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM
 AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE
 PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER.
 9. SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION
 (NAVD 88 AND NGVD 29).
 10. PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND
 STORMWATER FACILITIES ALONG ENTIRE PROJECT FRONTAGE.
 11. PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
 12. PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR
 PROPOSED SANITARY LATERALS.
 13. PLEASE LABEL WATER LINES AS PRIVATE WHERE
 APPLICABLE.
 14. PLEASE PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED
 LOCATION OF WATER METER AND BACKFLOW PREVENTION; CALL
 OUT HORIZONTAL SEPARATION OF PROPOSED WATER FROM
 EXISTING 8 IN. SANITARY LINE.
 15. PROPOSED DOMESTIC WATER TAP SHOWN CONNECTING TO
 EXISTING 8 IN. SANITARY LINE; PLEASE CORRECT.
 16. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING
 PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT
 HIM AT 561-494-2262 OR [email protected]
 17. PROVIDE DEDICATED UTILITY EASEMENTS TO ALLOW ACCESS
 FOR CITY PERSONNEL TO PROPOSED UTILITY WATER METERS.
  
  
  
 THE FOLLOWING COMMENTS ARE FROM HONG XU, PROJECT
 ENGINEER, CITY OF WPB PUBLIC UTILITIES, 561-494-1047,
 [email protected] :
  
 PLEASE CLARIFY IF 6 INCH POTABLE WATER SERVICE, 8 INCH
 DIP FIRE SERVICE AND 3 INCH IRRIGATION SERVICE ARE
 EXISTING OR PROPOSED. HOW DO THEY CONNECT TO EXISTING
 ONES?
  
 ARE THERE PROPOSED SEWER LATERALS CONNECTING TO
 EXISTING 8 INCH VCP SANITARY SEWER MAIN FROM THE
 PROPOSED BUILDING?
  
 ARE THERE ANY DRY UTILITIES THE AREA?
  
 PLEASE PROVIDE THE LEVEL OF SERVICE CALCULATION.
  
 THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES:
  
 -IS THE EXISTING PHASE ONE PROPERTY ADDRESS 350 S.
 AUSTRALIAN OR 300 S. AUSTRALIAN? EXISTING WATER
 SERVICES SHOW UP AS 300 S. AUSTRALIAN AVE IN UTILITY
 BILLING SYSTEM. PLEASE ALSO VERIFY ADDRESS OF PHASE TWO
 CONSTRUCTION.
  
 -IT APPEARS THERE ARE AT LEAST TWO EXISTING FIRE
 HYDRANTS ON WEST SIDE OF OPEN SPACE DOWNSTREAM OF
 EXISTING DCDA FIRELINE. WILL THOSE REMAIN IN SAME SPOT
 OR BE RELOCATED NEARBY?
  
 -EXISTING FIRE DCDA NEEDS TO REMAIN ADJACENT CLEARWATER
 DR. NEAR THE EASTERN PROPERTY LINE. ON FORMAL
 ENGINEERING SUBMITTAL PLEASE LABEL POINT OF SERVICE
 GATE VALVE.
  
 -EXISTING 6? DOMESTIC METER NEEDS TO BE INSTALLED
 ABOVE-GROUND WHEN RELOCATED WITHOUT A LARGE VAULT PER
 CONSTRUCTION STANDARD DETAILS. DO NOT REUSE WATER
 SERVICE COMPONENTS SUCH AS FITTINGS, BOXES, LIDS,
 VALVES, AND PIPING ? REPLACE THEM. PLAN THE WORK TO
 MINIMIZE WATER SERVICE OUTAGES FOR CUSTOMERS.
  
 -KEEP WATER METER BOX, BACKFLOW ASSEMBLIES, AND VALVE
 BOXES OUT OF SIDEWALKS AND PEDESTRIAN FOOT TRAFFIC.
  
 -RELOCATED BACKFLOW ASSEMBLIES WILL BE SUBJECT TO
 BACKFLOW INSTALLATION INSPECTIONS. ANY BACKFLOW
 ASSEMBLIES THAT ARE NOT LEAD-FREE COMPLIANT OR USC
 APPROVED WILL NEED TO BE REPLACED WITH COMPLIANT
 ASSEMBLIES.
  
 -EXISTING IRRIGATION METER IS 2?. IF NOT SUFFICIENT,
 MAY NEED TO UPSIZE OR ADD ADDITIONAL WATER SERVICE.
  
 -WATER SERVICES AND METERS (EXISTING OR PROPOSED) ON
 PRIVATE PROPERTY WILL REQUIRE UTILITY EASEMENT IF NOT
 EXISTING ALREADY. BACKFLOW ASSEMBLIES CANNOT BE IN
 UTILITY EASEMENTS.
  
 -NEED MORE INFORMATION ON LOCATION OF PROPOSED NEW
 WATER SERVICES AND BACKFLOW ASSEMBLIES. IS THAT
 LOCATION A GRASSY AREA WHERE THERE IS NO INTENTION OF
 PEDESTRIAN OR VEHICLE TRAFFIC? THEY CANNOT BE LOCATED
 IN ROADWAYS OR SIDEWALKS.
  
 -EXISTING FIRE HYDRANT NEAR SE CORNER OF PROPERTY
 APPEARS TO BE LEFT OFF OF UTILITY PLAN. PLEASE ADD AND
 LABEL.
  
 -PROPOSED DOMESTIC AND IRRIGATION WATER SERVICES WITH
 METERS 3? AND LARGER SHOULD BE ABOVE-GROUND
 INSTALLATION USING SD WS-3.
  
 -PLEASE RELOCATE PROPOSED WATER SERVICE PIPING SO THAT
 IT DOES NOT RUN UNDERNEATH AND CLOSE TO FPL/AT&T
 UTILITIES AND GUY WIRES. BUILDING STRUCTURE OR LOCATION
 MAY NEED REDESIGN/ALTERATION TO FACILITATE THIS. ALSO
 RELOCATE PROPOSED METERS CLOSER TO EASTERN PROPERTY
 LINE SO THEY ARE WITHIN REACH OF CRANETRUCK OR BACKHOE,
 AND PIPE DISTANCE TO WATER MAIN IS MINIMIZED.
  
 -VERIFY PROPOSED 8? DCDA LOCATION IS ACCEPTABLE WITH
 CITY WPB FIRE MARSHAL.
  
 -SOME PARTS OF THE PROPERTY LIMITS APPEAR TO BE LEFT
 OFF OF THE UTILITY PLANS. PLEASE ADD THOSE AREAS TO THE
 PLANS USING MATCH-LINES AND EXTRA SHEETS IF NECESSARY.
  
 -FOR FORMAL ENGINEERING SUBMITTAL ADD ENLARGED/ZOOMED
 AREA OF THE METERED WATER SERVICES AND BACKFLOW
 ASSEMBLIES.
  
 -WPB UTILITIES RECOMMENDS PARALLEL/DUAL BACKFLOW
 ASSEMBLIES ON LARGE DOMESTIC WATER SERVICES TO MINIMIZE
 WATER OUTAGES DURING BACKFLOW ASSEMBLY MAINTENANCE.
  
  
  