Plan Review Notes
Plan Review Notes For Project Z20080005
Project Number Z20080005
Review Stop ENG - PPRC
Sequence Number 1
Notes
Date Text
2020-09-03 09:45:43COMMENTS PER RICK ROSSANO, PROJECT COORD., CITY OF WPB
 ENG. SERVICES, 561-494-1098:
  
 1. PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1040 FOR FURTHER
 ASSISTANCE.
 2. PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS
 OF ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES,
 INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND
 SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES,
 METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE
 SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING
 GRADES, PIPES SIZES, MATERIALS, ELEVATIONS,
 ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL
 INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER
 LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN
 VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
 PLEASE SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL. ADDITIONALLY, PLAN VIEW SHALL SHOW ALL
 EXISTING AND PROPOSED UNDERGROUND UTILITY LAYOUT,
 INCLUDING FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED ON THE
 RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL
 UTILITY CROSSINGS.
 3. PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE
 DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB
 DEVELOPMENT APPLICATION).
 4. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND
 PROPOSED DEMANDS FOR WATER & SEWER IF ANY (AVERAGE,
 MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS
 SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008
 FOR WATER.
 5. SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION
 (NAVD 88 AND NGVD 29).
 6. PLEASE SHOW INLET PROTECTION FOR THE DRAINAGE INLET
 ON THE SOUTH SIDE OF UP THE GROVE LN. DIRECTLY ACROSS
 FROM THE PROPOSED DRIVEWAY WORK.
  
 THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES,
 PLEASE CONTACT 561-494-2262 OR [email protected]:
  
 -CREATE SEPARATE WATER OR UTILITY PLAN SHOWING EXISTING
 AND PROPOSED WATER SERVICES.
  
 -EXISTING WATER METER HAS HISTORICALLY REMAINED OUTSIDE
 OF FENCE AND NEEDS TO CONTINUE REMAINING OUTSIDE OF ANY
 FENCES AND ACCESSIBLE FROM THE STREET. CAN RELOCATE
 FENCE AROUND IT OR RELOCATE WATER SERVICE/METER.
  
 -DEMO PLAN SHOWS AN UNDERGROUND VAULT ADJACENT WATER
 METER BOX. IF THAT CONTAINS AN UNDERGROUND BACKFLOW
 ASSEMBLY IT MUST BE CONVERTED TO ABOVE-GROUND
 INSTALLATION AND BROUGHT UP TO STANDARDS.
  
 -VERIFY WHERE BACKFLOW ASSEMBLY FOR EXISTING WATER
 SERVICE IS LOCATED.
  
 -VERIFY IF THE EXISTING WATER SERVICE AND METER IS FOR
 4301 UP THE GROVE OR 5950 N MILITARY TRL. DOES 4301
 NEED CITY WATER AND CURRENTLY USE ANY?
  
 -UTILITY EASEMENT MUST BE GRANTED FOR WATER SERVICE AND
 METER BOX ON PROPERTY IF NONE CURRENTLY EXIST.
  
 -APPEARS SOMETHING TRIANGULAR AND LARGE IS BEING BUILT
 ON AND AROUND THE WATER SERVICE. PLEASE ADVISE WHAT
 THIS IS. IF THIS IS SOME KIND OF WATER RETENTION AREA,
 WATER METER AND BACKFLOW ASSEMBLY WOULD HAVE TO BE
 RELOCATED OUT OF THE AREA. STRUCTURES ALSO MAY NOT
 ENCROACH ON WATER SERVICES AND METER BOXES.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 DIRECT: (561) 494-1098 [email protected]
  
  