| 2021-05-29 09:56:51 | THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD |
| | CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES, |
| | PLEASE CONTACT 561-494-2262 OR [email protected]: |
| | FOLLOWUPS TO RESPONSES: |
| | |
| | 12. IF FIRELINE PIPING IS GOING TO RUN THROUGH |
| | POND/LAKE, THEN BOTH CONTAINMENT FIRELINE BACKFLOW |
| | ASSEMBLIES WOULD NEED TO BE UPGRADED TO RPDA TYPES. |
| | |
| | PAGE 9 KIMLEY-HORN.COM 1615 SOUTH CONGRESS AVENUE, |
| | SUITE 201, DELRAY BEACH, FL 33445 561 330 2345 |
| | RESPONSE: FIRELINE PIPES RUNNING UNDER DRY DETENTION |
| | AREA HAVE BEEN REVISED TO BE RPDA TYPE, REFER TO SHEET |
| | C501.0. |
| | |
| | -DURING SITE MEETING, ENGINEER VERIFIED NO INCREASED |
| | HAZARD DUE TO LINER. I BELIEVE THE INTENTION WAS TO |
| | KEEP USING BOTH EXISTING FIRELINE DDCV IF THEY ARE NOT |
| | BEING RELOCATED. |
| | |
| | NEW COMMENTS AS FOLLOWS: |
| | |
| | -THERE MAY BE LANDSCAPING CONFLICTS WITH UTILITIES BUT |
| | CANNOT TELL FOR SURE BECAUSE LANDSCAPING PLAN DOES NOT |
| | SHOW UTILITIES ON IT. PLEASE SUBMIT SEPARATE PLAN SHEET |
| | WITH LANDSCAPING OVERLAID ON UTILITIES SO CAN VERIFY |
| | BETTER. |
| | |
| | -PRIOR ASKED ABOUT IRRIGATION AND RESPONSE REFERENCED |
| | IRRIGATION PLAN. CANNOT FIND THE IRRIGATION PLAN ? |
| | PLEASE SUBMIT IT. |
| | |
| | -CIVIL PLANS HAD DUPLICATE STANDARD DETAILS INCLUDE FOR |
| | SMALL BACKFLOW ASSEMBLY. PLEASE REMOVE ONE OF THE THEM. |
| | |
| | -IS EXISTING PRIVATE LIFT STATION SUFFICIENT FOR |
| | ADDITION OF BJ?S? |
| | |
| | -GREASETRAP FOR BRANDSMART LOOKS LIKE IT IS LOCATED IN |
| | THE ROAD. DID NOT KNOW IF THAT WOULD COMPLICATE |
| | MAINTENANCE. IS LOCATION ACCEPTABLE? |
| | |
| | -COULD ONLY FIND A SEWER LATERAL FOR BRANDSMART GOING |
| | TO A GREASETRAP. IF THERE IS ANOTHER ONE, PLEASE SHOW |
| | AND LABEL IT ON SEWER PLAN. |
| | |
| | -LABEL BOTH FPL STATIONS ON THE WATER PLAN. IF THERE |
| | ARE ANY EASEMENTS FOR THE FPL STATIONS, THEN SHOW AND |
| | LABEL THOSE ALSO. |
| | |
| | -SHOW AND LABEL PROPOSED MONUMENT SIGNS ON THE WATER |
| | PLANS. (THEY ARE SHOWN ON THE SITE PLAN FOR REFERENCE). |
| | |
| | -FOR FORMAL ENGINEERING SUBMITTAL: SHOW AND LABEL |
| | EXISTING FIRELINE AROUND SOUTHERN AND WESTERN PORTIONS |
| | OF BRANDSMART ALL THE WATER TO THE WATER MAIN ? (SOME |
| | PORTIONS ARE MISSING), SHOW BETTER ON INSET B THE |
| | CONNECTION FROM NEW 4 INCH PIPE TO 2.5 INCH BACKFLOW |
| | ASSEMBLIES. |
| | |
| | -MAKE SURE WATER PLAN DOMESTIC BACKFLOW ASSEMBLY |
| | INFORMATION NEAR NE ROW MATCHES INSET A. SHOULD NOT BE |
| | DDCV OR RPDA ? SHOULD BE RP TYPE. BELIEVE THOSE WERE |
| | PROPOSED TO BE REPLACED. |
| | |
| | -SAN SEWER MH NORTHEAST OF MH NO.1 IS NOT LABELED WITH |
| | ELEVATION INFO. |
| | |
| | -PIPE SIZING FOR FIRE HYDRANT ON INSET B DOES NOT SEEM |
| | TO MATCH CROSSING INFORMATION AND PLAN SIZING. |
| | |
| | -DEMOLITION PLAN IS AMBIGUOUS ON HOW THE WATER PIPING |
| | WILL BE DEMOLISHED. FOR INSTANCE THE EXISTING 10 WATER |
| | PIPE. PLEASE INCLUDE MORE DETAIL ON THE PLAN THE METHOD |
| | OF DEMOLITION. |
| | -ON DEMO PLAN ADD PIPE MATERIAL TYPE TO LABEL FOR |
| | EXISTING 10 WATER PIPE THAT IS TO BE DEMOLISHED. |
| | |
| | |
| |