Plan Review Notes
Plan Review Notes For Project Z20070016
Project Number Z20070016
Review Stop ENG - PPRC
Sequence Number 3
Notes
Date Text
2021-05-29 09:56:51THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES,
 PLEASE CONTACT 561-494-2262 OR [email protected]:
 FOLLOWUPS TO RESPONSES:
  
 12. IF FIRELINE PIPING IS GOING TO RUN THROUGH
 POND/LAKE, THEN BOTH CONTAINMENT FIRELINE BACKFLOW
 ASSEMBLIES WOULD NEED TO BE UPGRADED TO RPDA TYPES.
  
 PAGE 9 KIMLEY-HORN.COM 1615 SOUTH CONGRESS AVENUE,
 SUITE 201, DELRAY BEACH, FL 33445 561 330 2345
 RESPONSE: FIRELINE PIPES RUNNING UNDER DRY DETENTION
 AREA HAVE BEEN REVISED TO BE RPDA TYPE, REFER TO SHEET
 C501.0.
  
 -DURING SITE MEETING, ENGINEER VERIFIED NO INCREASED
 HAZARD DUE TO LINER. I BELIEVE THE INTENTION WAS TO
 KEEP USING BOTH EXISTING FIRELINE DDCV IF THEY ARE NOT
 BEING RELOCATED.
  
 NEW COMMENTS AS FOLLOWS:
  
 -THERE MAY BE LANDSCAPING CONFLICTS WITH UTILITIES BUT
 CANNOT TELL FOR SURE BECAUSE LANDSCAPING PLAN DOES NOT
 SHOW UTILITIES ON IT. PLEASE SUBMIT SEPARATE PLAN SHEET
 WITH LANDSCAPING OVERLAID ON UTILITIES SO CAN VERIFY
 BETTER.
  
 -PRIOR ASKED ABOUT IRRIGATION AND RESPONSE REFERENCED
 IRRIGATION PLAN. CANNOT FIND THE IRRIGATION PLAN ?
 PLEASE SUBMIT IT.
  
 -CIVIL PLANS HAD DUPLICATE STANDARD DETAILS INCLUDE FOR
 SMALL BACKFLOW ASSEMBLY. PLEASE REMOVE ONE OF THE THEM.
  
 -IS EXISTING PRIVATE LIFT STATION SUFFICIENT FOR
 ADDITION OF BJ?S?
  
 -GREASETRAP FOR BRANDSMART LOOKS LIKE IT IS LOCATED IN
 THE ROAD. DID NOT KNOW IF THAT WOULD COMPLICATE
 MAINTENANCE. IS LOCATION ACCEPTABLE?
  
 -COULD ONLY FIND A SEWER LATERAL FOR BRANDSMART GOING
 TO A GREASETRAP. IF THERE IS ANOTHER ONE, PLEASE SHOW
 AND LABEL IT ON SEWER PLAN.
  
 -LABEL BOTH FPL STATIONS ON THE WATER PLAN. IF THERE
 ARE ANY EASEMENTS FOR THE FPL STATIONS, THEN SHOW AND
 LABEL THOSE ALSO.
  
 -SHOW AND LABEL PROPOSED MONUMENT SIGNS ON THE WATER
 PLANS. (THEY ARE SHOWN ON THE SITE PLAN FOR REFERENCE).
  
 -FOR FORMAL ENGINEERING SUBMITTAL: SHOW AND LABEL
 EXISTING FIRELINE AROUND SOUTHERN AND WESTERN PORTIONS
 OF BRANDSMART ALL THE WATER TO THE WATER MAIN ? (SOME
 PORTIONS ARE MISSING), SHOW BETTER ON INSET B THE
 CONNECTION FROM NEW 4 INCH PIPE TO 2.5 INCH BACKFLOW
 ASSEMBLIES.
  
 -MAKE SURE WATER PLAN DOMESTIC BACKFLOW ASSEMBLY
 INFORMATION NEAR NE ROW MATCHES INSET A. SHOULD NOT BE
 DDCV OR RPDA ? SHOULD BE RP TYPE. BELIEVE THOSE WERE
 PROPOSED TO BE REPLACED.
  
 -SAN SEWER MH NORTHEAST OF MH NO.1 IS NOT LABELED WITH
 ELEVATION INFO.
  
 -PIPE SIZING FOR FIRE HYDRANT ON INSET B DOES NOT SEEM
 TO MATCH CROSSING INFORMATION AND PLAN SIZING.
  
 -DEMOLITION PLAN IS AMBIGUOUS ON HOW THE WATER PIPING
 WILL BE DEMOLISHED. FOR INSTANCE THE EXISTING 10 WATER
 PIPE. PLEASE INCLUDE MORE DETAIL ON THE PLAN THE METHOD
 OF DEMOLITION.
 -ON DEMO PLAN ADD PIPE MATERIAL TYPE TO LABEL FOR
 EXISTING 10 WATER PIPE THAT IS TO BE DEMOLISHED.
  
  