| 2020-12-03 08:47:09 | 1. THE CITY OF WEST PALM BEACH HAS A NUMBER OF |
| | REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY |
| | AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND |
| | WASTEWATER UTILITIES WITHIN THE CITY. TO VIEW |
| | DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AND OTHER |
| | ENGINEERING RELATED DOCUMENTS, OPEN A BROWSER IN CHROME |
| | AND GO TO: WWW.WPB.ORG/ENGDOCS . TO LOGIN, UNDER |
| | ?EMAIL? ENTER [email protected] ; UNDER ?PASSWORD? ENTER |
| | SIMPLE321# |
| | THERE ARE 4 PAGES OF AVAILABLE ENGINEERING DOCUMENTS |
| | FOR YOUR USE. |
| | 2. CODE OF ORDINANCES, CITY OF WEST PALM BEACH, |
| | FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED |
| | SEPT. 22, 2008. (SUPPLEMENT NO. 18) CHAPTER 90 |
| | UTILITIES, ARTICLE I. SEC. 90-7. |
| | POLICY REGARDING EXTENSION OF WATER OR SEWER SERVICE |
| | FACILITIES OF THE CITY: |
| | THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE |
| | CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY |
| | BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS, |
| | BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION. |
| | 3. AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH |
| | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, |
| | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR |
| | MORE INFORMATION, OPEN A BROWSER IN CHROME AND GO TO: |
| | WWW.WPB.ORG/ENGDOCS .TO LOGIN, UNDER ?EMAIL? ENTER |
| | [email protected] ; UNDER ?PASSWORD? ENTER SIMPLE321# |
| | CROSS-CONNECTION CONTROL MANUAL IS ON PAGE 4. |
| | 4. PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY |
| | OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC |
| | RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF |
| | YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE |
| | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL |
| | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT |
| | [email protected] OR 561-494-1040 FOR FURTHER |
| | ASSISTANCE. |
| | 5. PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS |
| | OF ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES, |
| | INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND |
| | SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES, |
| | METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE |
| | SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING |
| | GRADES, PIPES SIZES, MATERIALS, ELEVATIONS, |
| | ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL |
| | INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER |
| | LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE |
| | PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN |
| | VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS. |
| | PLEASE SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT |
| | MATERIAL. ADDITIONALLY, PLAN VIEW SHALL SHOW ALL |
| | EXISTING AND PROPOSED UNDERGROUND UTILITY LAYOUT, |
| | INCLUDING FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION & |
| | TELECOMMUNICATION FACILITIES LOCATED ON THE |
| | RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL |
| | UTILITY CROSSINGS. |
| | 6. CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY |
| | ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY |
| | ROW. |
| | 7. PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE |
| | DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB |
| | DEVELOPMENT APPLICATION). |
| | 8. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND |
| | PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM |
| | AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE |
| | PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER. |
| | 9. SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION |
| | (NAVD 88 AND NGVD 29). |
| | 10. PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND |
| | STORMWATER ALONG ENTIRE PROJECT FRONTAGE. |
| | 11. PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND |
| | IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED |
| | AREAS. |
| | 12. PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR |
| | PROPOSED SANITARY LATERALS. |
| | 13. PLEASE LABEL WATER LINES AS PRIVATE WHERE |
| | APPLICABLE. |
| | 14. PLEASE PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED |
| | LOCATION OF WATER METER AND BACKFLOW PREVENTION. |
| | 15. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE |
| | SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING |
| | PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT |
| | HIM AT 561-494-2262 OR [email protected] |
| | 16. PROVIDE DEDICATED UTILITY EASEMENTS TO ALLOW ACCESS |
| | FOR CITY PERSONNEL TO PROPOSED UTILITY WATER METERS. |
| | |
| | THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD |
| | CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES, |
| | PLEASE CONTACT 561-494-2262 OR [email protected]: |
| | |
| | -ALL CURRENT WATER SERVICES AROUND BRANDSMART AT |
| | EXECUTIVE CENTER HAVE UTILITY BILLS IN BRANDSMART?S |
| | NAME AND ON SITE PIPING LOOKS TO BE OWNED BY THEM. THE |
| | PROPOSED PROPERTY LINES AND WATER USAGE IS PRECARIOUS |
| | BECAUSE PRIVATELY-OWNED PIPING IS CROSSING PROPERTY |
| | LINES, AND WATER USE IN SOME INSTANCES APPEARS TO BE |
| | COMING FROM METERED WATER SERVICES THE USER WOULD NOT |
| | PAY FOR. TO PREVENT PRACTICAL AND LEGAL CONFUSION AND |
| | PROBLEMS IN THE FUTURE, RECOMMEND WATER SERVICES AND |
| | PIPING TO BE DESIGNED IN CONJUNCTION WITH THE PROPERTY |
| | LINES, SUCH THAT THE PIPING AND WATER USAGE IS |
| | CONTAINED TO EACH PROPERTY. |
| | -REMOVAL OF EXISTING FIRE HYDRANTS WOULD REQUIRE THE |
| | APPROVAL OF CITY WPB FIRE MARSHAL. |
| | -THERE ARE SEVERAL FIRE HYDRANTS ON THE WATER PLANS |
| | THAT DO NOT HAVE NOTES ON WHAT IS HAPPENING TO THEM. |
| | PLEASE ADD LABELING IF THEY ARE REMAINING OR BEING |
| | REMOVED. |
| | -C501.0 APPEARS TO BE MISSING THE EXISTING DOMESTIC |
| | VAULT WATER SERVICE. PLEASE ADD TO PLAN AND LABEL. |
| | -C501.1 APPEARS TO BE MISSING A LARGE DOMESTIC WATER |
| | SERVICE. PLEASE ADD TO PLAN AND LABEL. |
| | -LABEL PRIVATE FIRELINES. NOTE THAT FIRELINES MAY ONLY |
| | BE USED FOR FIREFIGHTING PURPOSES AND CANNOT BE TAPPED |
| | FOR THINGS LIKE HOSE BIBS. VERIFY THAT NOT HAPPENING |
| | WITH AREA AROUND PROPOSED GAS STATION. |
| | -ON SHEET C501.0, PROPOSED METER IS IN SIDEWALK. CANNOT |
| | INSTALL METER IN SIDEWALK. RELOCATE TO GRASS AREA AND |
| | ADD UTILITY EASEMENT IF ON PRIVATE PROPERTY. |
| | -ADD NOTE TO PLAN TO COORDINATE WATER UTILITY WORK SUCH |
| | THAT DOWNTIME/OUTAGES OF WATER SERVICES AND FIRELINES |
| | ARE MINIMIZED. |
| | -ADD NOTE TO PLAN TO NOTIFY WPB FIRE DEPARTMENT IF ANY |
| | FIRELINE OR FIRE HYDRANT IS RENDERED NONFUNCTIONAL OR |
| | TAKEN OUT OF SERVICE TEMPORARILY. |
| | -CANNOT DISTINGUISH WATER SERVICES AT CITY POINT OF |
| | SERVICE. ADD SEPARATE DETAILED BLOWUP PLANS SHOWING THE |
| | AREAS AROUND THE WATER METERS AND BACKFLOW ASSEMBLIES. |
| | -APPEARS SOME BACKFLOW ASSEMBLIES AND WATER SERVICES |
| | ARE MISSING FROM WATER PLANS. PLEASE ADD AND LABEL. |
| | -SEVERAL EXISTING BACKFLOW ASSEMBLIES ON SITE ARE |
| | LEAKING AND NEED REPAIR. ADD NOTE TO PLAN THAT ANY |
| | LEAKING BACKFLOW ASSEMBLIES NEED TO BE REPAIRED OR |
| | REPLACED BY PROJECT COMPLETION. |
| | -ADD WATER DEMAND CALCULATIONS TO WATER PLANS. |
| | -WATER SERVICE STANDARD DETAILS ARE OLD REVISION. NEED |
| | UPDATE TO NEWEST REVISION FOR ANY THAT WILL BE USED. |
| | NEED INCLUDE WATER SERVICE STANDARD DETAILS FOR SMALL |
| | WATER SERVICE AND SMALL BACKFLOW ASSEMBLY. |
| | -PROPOSED PROPERTY LINE FOR GAS STATION IS NOT |
| | CONNECTING TO BJ?S MAIN PROPERTY. THIS COULD BE |
| | PROBLEMATIC IF BRANDSMART DOES NOT ALLOW ACCESS OR |
| | BUILDS SOMETHING THAT WOULD CUT OFF ACCESS. |
| | -PLEASE VERIFY IF BJ?S WILL HAVE FIRE SPRINKLERS INSIDE |
| | BUILDING. |
| | -DID NOT SEE SEPARATE METERED IRRIGATION WATER SERVICE |
| | FOR BJ?S. WILL ONE BE NEEDED? |
| | |
| |