Plan Review Notes
Plan Review Notes For Project Z20070016
Project Number Z20070016
Review Stop ENG - PPRC
Sequence Number 1
Notes
Date Text
2020-12-03 08:47:091. THE CITY OF WEST PALM BEACH HAS A NUMBER OF
 REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY
 AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND
 WASTEWATER UTILITIES WITHIN THE CITY. TO VIEW
 DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AND OTHER
 ENGINEERING RELATED DOCUMENTS, OPEN A BROWSER IN CHROME
 AND GO TO: WWW.WPB.ORG/ENGDOCS . TO LOGIN, UNDER
 ?EMAIL? ENTER [email protected] ; UNDER ?PASSWORD? ENTER
 SIMPLE321#
 THERE ARE 4 PAGES OF AVAILABLE ENGINEERING DOCUMENTS
 FOR YOUR USE.
 2. CODE OF ORDINANCES, CITY OF WEST PALM BEACH,
 FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED
 SEPT. 22, 2008. (SUPPLEMENT NO. 18) CHAPTER 90
 UTILITIES, ARTICLE I. SEC. 90-7.
 POLICY REGARDING EXTENSION OF WATER OR SEWER SERVICE
 FACILITIES OF THE CITY:
 THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
 3. AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, OPEN A BROWSER IN CHROME AND GO TO:
 WWW.WPB.ORG/ENGDOCS .TO LOGIN, UNDER ?EMAIL? ENTER
 [email protected] ; UNDER ?PASSWORD? ENTER SIMPLE321#
 CROSS-CONNECTION CONTROL MANUAL IS ON PAGE 4.
 4. PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1040 FOR FURTHER
 ASSISTANCE.
 5. PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS
 OF ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES,
 INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND
 SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES,
 METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE
 SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING
 GRADES, PIPES SIZES, MATERIALS, ELEVATIONS,
 ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL
 INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER
 LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN
 VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
 PLEASE SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL. ADDITIONALLY, PLAN VIEW SHALL SHOW ALL
 EXISTING AND PROPOSED UNDERGROUND UTILITY LAYOUT,
 INCLUDING FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED ON THE
 RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL
 UTILITY CROSSINGS.
 6. CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 ROW.
 7. PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE
 DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB
 DEVELOPMENT APPLICATION).
 8. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND
 PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM
 AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE
 PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER.
 9. SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION
 (NAVD 88 AND NGVD 29).
 10. PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND
 STORMWATER ALONG ENTIRE PROJECT FRONTAGE.
 11. PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
 12. PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR
 PROPOSED SANITARY LATERALS.
 13. PLEASE LABEL WATER LINES AS PRIVATE WHERE
 APPLICABLE.
 14. PLEASE PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED
 LOCATION OF WATER METER AND BACKFLOW PREVENTION.
 15. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING
 PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT
 HIM AT 561-494-2262 OR [email protected]
 16. PROVIDE DEDICATED UTILITY EASEMENTS TO ALLOW ACCESS
 FOR CITY PERSONNEL TO PROPOSED UTILITY WATER METERS.
  
 THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES,
 PLEASE CONTACT 561-494-2262 OR [email protected]:
  
 -ALL CURRENT WATER SERVICES AROUND BRANDSMART AT
 EXECUTIVE CENTER HAVE UTILITY BILLS IN BRANDSMART?S
 NAME AND ON SITE PIPING LOOKS TO BE OWNED BY THEM. THE
 PROPOSED PROPERTY LINES AND WATER USAGE IS PRECARIOUS
 BECAUSE PRIVATELY-OWNED PIPING IS CROSSING PROPERTY
 LINES, AND WATER USE IN SOME INSTANCES APPEARS TO BE
 COMING FROM METERED WATER SERVICES THE USER WOULD NOT
 PAY FOR. TO PREVENT PRACTICAL AND LEGAL CONFUSION AND
 PROBLEMS IN THE FUTURE, RECOMMEND WATER SERVICES AND
 PIPING TO BE DESIGNED IN CONJUNCTION WITH THE PROPERTY
 LINES, SUCH THAT THE PIPING AND WATER USAGE IS
 CONTAINED TO EACH PROPERTY.
 -REMOVAL OF EXISTING FIRE HYDRANTS WOULD REQUIRE THE
 APPROVAL OF CITY WPB FIRE MARSHAL.
 -THERE ARE SEVERAL FIRE HYDRANTS ON THE WATER PLANS
 THAT DO NOT HAVE NOTES ON WHAT IS HAPPENING TO THEM.
 PLEASE ADD LABELING IF THEY ARE REMAINING OR BEING
 REMOVED.
 -C501.0 APPEARS TO BE MISSING THE EXISTING DOMESTIC
 VAULT WATER SERVICE. PLEASE ADD TO PLAN AND LABEL.
 -C501.1 APPEARS TO BE MISSING A LARGE DOMESTIC WATER
 SERVICE. PLEASE ADD TO PLAN AND LABEL.
 -LABEL PRIVATE FIRELINES. NOTE THAT FIRELINES MAY ONLY
 BE USED FOR FIREFIGHTING PURPOSES AND CANNOT BE TAPPED
 FOR THINGS LIKE HOSE BIBS. VERIFY THAT NOT HAPPENING
 WITH AREA AROUND PROPOSED GAS STATION.
 -ON SHEET C501.0, PROPOSED METER IS IN SIDEWALK. CANNOT
 INSTALL METER IN SIDEWALK. RELOCATE TO GRASS AREA AND
 ADD UTILITY EASEMENT IF ON PRIVATE PROPERTY.
 -ADD NOTE TO PLAN TO COORDINATE WATER UTILITY WORK SUCH
 THAT DOWNTIME/OUTAGES OF WATER SERVICES AND FIRELINES
 ARE MINIMIZED.
 -ADD NOTE TO PLAN TO NOTIFY WPB FIRE DEPARTMENT IF ANY
 FIRELINE OR FIRE HYDRANT IS RENDERED NONFUNCTIONAL OR
 TAKEN OUT OF SERVICE TEMPORARILY.
 -CANNOT DISTINGUISH WATER SERVICES AT CITY POINT OF
 SERVICE. ADD SEPARATE DETAILED BLOWUP PLANS SHOWING THE
 AREAS AROUND THE WATER METERS AND BACKFLOW ASSEMBLIES.
 -APPEARS SOME BACKFLOW ASSEMBLIES AND WATER SERVICES
 ARE MISSING FROM WATER PLANS. PLEASE ADD AND LABEL.
 -SEVERAL EXISTING BACKFLOW ASSEMBLIES ON SITE ARE
 LEAKING AND NEED REPAIR. ADD NOTE TO PLAN THAT ANY
 LEAKING BACKFLOW ASSEMBLIES NEED TO BE REPAIRED OR
 REPLACED BY PROJECT COMPLETION.
 -ADD WATER DEMAND CALCULATIONS TO WATER PLANS.
 -WATER SERVICE STANDARD DETAILS ARE OLD REVISION. NEED
 UPDATE TO NEWEST REVISION FOR ANY THAT WILL BE USED.
 NEED INCLUDE WATER SERVICE STANDARD DETAILS FOR SMALL
 WATER SERVICE AND SMALL BACKFLOW ASSEMBLY.
 -PROPOSED PROPERTY LINE FOR GAS STATION IS NOT
 CONNECTING TO BJ?S MAIN PROPERTY. THIS COULD BE
 PROBLEMATIC IF BRANDSMART DOES NOT ALLOW ACCESS OR
 BUILDS SOMETHING THAT WOULD CUT OFF ACCESS.
 -PLEASE VERIFY IF BJ?S WILL HAVE FIRE SPRINKLERS INSIDE
 BUILDING.
 -DID NOT SEE SEPARATE METERED IRRIGATION WATER SERVICE
 FOR BJ?S. WILL ONE BE NEEDED?
  