| 2020-08-12 20:10:01 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. |
| | |
| | 2. FLOOD ZONE. ACCORDING TO THE ADOPTED FLOOD INSURANCE |
| | RATE MAPS (FIRMS), THE PROPOSED BUILDING IS IN FLOOD |
| | ZONE AE, WITH A BASE FLOOD ELEVATION OF 14 FT NAVD. THE |
| | FIRST FLOOR OF THE BUILDING AND ALL ASSOCIATED |
| | MECHANICAL EQUIPMENT (CHILLERS, GENERATORS ETC.) SHALL |
| | BE 24 INCHES (FREEBOARD) ABOVE THE BASE FLOOD |
| | ELEVATION. |
| | |
| | 3. NUMBER OF ACCESSIBLE PARKING SPACES. SITE PLAN SHEET |
| | SP.1 SHOWS A TOTAL OF 43 PROPOSED PARKING SPACES BUT |
| | SHOWS ONLY 1 ACCESSIBBLE PARKING SPACE. 2 ACCESSIBLE |
| | PARKING SPACES ARE REQUIRED. THE TOTAL MINIMUM NUMBER |
| | OF ACCESSIBLE PARKING SPACES PROVIDED SHALL BE IN |
| | ACCORDANCE WITH SECTION 208.2 OF FLORIDA ACCESSIBILITY |
| | CODE. |
| | |
| | 4. LOCATION OF ACCESSIBLE PARKING SPACES. PER SECTION |
| | 208.3 OF FLORIDA ACCESSIBILITY CODE, ACCESSIBLE PARKING |
| | SPACES ARE TO BE LOCATED ON THE SHORTEST POSSIBLE ROUTE |
| | OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE |
| | ENTRANCE. THE DESIGN OF ACCESSIBLE PARKING SPACES SHALL |
| | COMPLY WITH SECTION 502 OF FLORIDA ACCESSIBILITY CODE |
| | |
| | 5. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, |
| | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR |
| | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, |
| | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE |
| | FLORIDA BUILDING CODE. |
| | |
| | 6. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, |
| | FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, |
| | GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, |
| | SITE IRRIGATION, ETC. |
| | |
| | 7. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT |
| | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL |
| | HAVE A SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT |
| | CAROLINE PUELL, ADDRESSING COORDINATOR, AT (561) 805 |
| | 6659, OR BY EMAIL: [email protected] |
| | |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |