Plan Review Notes For Project Z20060015
Project Number Z20060015
Review Stop STORM
Sequence Number 3
Notes
Date Text
2020-11-02 22:52:04THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 10/14/2020 SUBMITTAL PACKAGE. THEY CAN BE ADDRESSED
 DURING ENGINEERING PERMIT SUBMITTAL.
  
 1. ADD VERTICAL DATUM REFERENCE AND CONVERSION EQUATION
 TO NGVD1929 FOR THE TBM'S ON SHEET C-04.
  
 2. CHANGE SPELLING OF CULVER CANAL TO CARVER CANAL ON
 SHEET C-04.
  
 3. SHEET C-14 SHOWS PROPOSED MINIMUM PERIMETER
 ELEVATION OF 15.83 FEET NAVD1988. SECTION D-D ON THE
 SAME SHEET SHOWS BERM TO BE BETWEEN 16.85 AND 17.51
 FEET NAVD AND GRADE AT PROPERTY LINE BETWEEN 17.1 AND
 17.5 FEET NAVD. WOULD A SWALE INSTEAD OF A BERM BE MORE
 APPROPRIATE ALONG THE EAST PROPERTY LINE?
  
 4. THE YARD DRAIN APPEAR TO BE CONNECTED TO THE ONSITE
 DRAINAGE SYSTEM. WHY DO THEY NEED TO BE PERFORATED
 BASINS AS INDICATED IN THE YARD DRAIN DETAIL ON SHEET
 C-14?
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  