Plan Review Notes
Plan Review Notes For Project Z20060015
Project Number Z20060015
Review Stop ENG - PPRC
Sequence Number 3
Notes
Date Text
2020-10-19 13:55:21PASSED WITH PROVISOS:
  
 ZONING APPROVAL IS NECESSARY PRIOR TO FORMAL
 ENGINEERING SUBMITTAL.
  
 THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES,
 PLEASE CONTACT 561-494-2262 OR [email protected]:
  
 SHEET C-11
 -REPLACE STANDARD DETAIL WS-8 WITH WS-1. (METER BOXES
 NOT IN SIDEWALKS)
 -REMOVE WS-12. (NOT NEEDED AS INSTALLING RP?S AND WS-6
 ALREADY INCLUDED)
 -#2 ON ENLARGED PLAN SAYS USE EXISTING BOX FOR 1.5 IN.
 METER, BUT THE BOX IS TOO SMALL FOR THAT. WOULD HAVE TO
 REPLACE WITH BIGGER FLARED WALL METER BOX THAT HAS 17
 IN. X 30 IN. LID. (NEED TO ALSO UPDATE SIMILAR NOTES ON
 SHEET C-6)
  
 SHEET C-6
 -IS THE MILLING AND RESURFACING ON AUSTRALIAN AV. JUST
 FOR THE FIRE HYDRANT INSTALLATION ON THE WATER MAIN? IF
 SO, THEN IT MAY NOT BE NEEDED IF THE WATER MAIN IS
 FOUND TO BE IN THE MIDDLE OF THE GRASS PARKWAY INSTEAD
 OF ON EDGE OF ROAD. COULD ADD NOTE TO VERIFY IF IT
 REQUIRED AFTER FIRE HYDRANT INSTALLATION IS COMPLETE.
 -PLAN DOES NOT SHOW NUMERICAL PROPERTY ADDRESS AND DOES
 NOT HAVE A RECENT REVISION DATE. PLEASE ADD TO FORMAL
 ENGINEERING SUBMITTAL.
 -THE MIDDLE WATER SERVICE OF THREE IS NOT DRAWN. PLEASE
 ADD TO FORMAL ENGINEERING SUBMITTAL.
  
 ADDITIONAL COMMENTS FROM OCT 7 2020 ZOOM MEETING WITH
 LAURA LE, SUZANNE BERGLUND, TRACY WARD, DANA GILLETTE,
 STEPHON HARRIS TO BE ADRESSED WITH NEXT SUBMITTAL:
  
 SEWER
 1. THE CLEAN OUT SHOULD BE MOVED TO BEHIND THE SIDEWALK
 WITH A CONCRETE COLLAR.
 2. THE SEWER LATERAL SHOULD BE LINED DUE TO A CRACK IN
 THE PIPE NEAR THE MANHOLE. SUZANNE WILL PROVIDE THE
 CITY STANDARD SPEC.
 3. ADD A NOTE THAT THE CONTRACTOR IS TO COORDINATE WITH
 THE CITY UTILITY DEPT FOR WORK ON THE CITY?S WATER AND
 SEWER LINES.
 4. ADD A NOTE THAT THE CONTRACTOR IS TO OBTAIN A POST
 CONSTRUCTION CCTV OF THE SEWER LATERAL.
 5. THERE IS AN UNKNOWN UTILITY LINE. ADD A NOTE THAT
 THE CONTRACTOR IS TO LOCATE ALL PIPES/UTILITIES THAT
 ARE DISCOVERED/ CROSSED AND PROVIDE THEIR LOCATION ON
 THE AS BUILTS.
 6. ADD THE RIGHT OF WAY LINE TO THE PLANS.
 7. ADD A UTILITY EASEMENT AROUND THE NEW CLEAN OUT.
 8. LAURA NOTED THAT THERE IS A FORCE MAIN ON THE SOUTH
 SIDE OF 15TH ST, BUT THAT IT IS OUTSIDE OF THE PROPOSED
 WORK AREA.
  
 WATER SERVICE
 9. DANA NOTED THAT SHE?S BEEN COORDINATING WITH MARK
 HURLEY ABOUT THE WATER SERVICE CONFIGURATION. LAURA
 NOTED THAT IF THE 4? LINE, OR ANY OF THE THREE
 SERVICES, HAS AN ISSUE THEN ALL THREE SERVICES WILL BE
 IMPACTED. DANA NOTED THAT SINCE TWO ARE IRRIGATION
 LINES, THEY CAN BE TAKEN OUT OF SERVICE WITHOUT SERIOUS
 IMPACT.
 10. ADD THE FOLLOWING TO THE WATER SERVICE SKETCH:
 MATERIAL OF THE 4? PIPE (CAST IRON), LOCATION OF THE
 CAP, LOCATION OF THE 1? COPPER, NOTE TO CAP THE 1?
 COPPER AT THE MAIN, NOTE THAT THE AS-BUILTS ARE TO
 INCLUDE DETAILS OF THE SERVICE SKETCH AND ANY CAPPED
 LINES.
 11. ADD TO THE TABLE HOW WE DID THE MATH TO DETERMINE
 THE FLOW FOR THE WATER AND SEWER.
  
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 DIRECT: (561) 494-1098 [email protected]
  
  