2020-08-27 12:47:06THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES,
 PLEASE CONTACT 561-494-2262 OR [email protected]:
  
 FOLLOWUP COMMENTS CONCERNING SHEET C-06:
 WATER SERVICES AND METERS APPEAR TO STILL NOT BE
 ACCURATE RELATED TO EXISTING CONDITIONS ON SITE. THE
 EASTERN EXISTING METER HAS NO DAMAGE (I THINK THE BOX
 WAS REPLACED RECENTLY) AND IS THE ? IN. METER
 HISTORICALLY USED FOR DOMESTIC WATER AT THE PROPERTY.
 THAT METER COULD NOT BE UPGRADED TO 2 IN. AS THE
 SERVICE LINE IS SMALL. THE WESTERN EXISTING METER AT
 SOUTH END OF PROPERTY IS THE PARKS DEPARTMENT 1.5 IN.
 IRRIGATION METER THAT MR. KRISCHE ADVISED IN JULY 2020
 NEEDED TO REMAIN IN TACT FOR FUTURE USE ? ONLY LABEL
 ?PARK DEPARTMENT TO REMOVE? IF PARKS REPRESENTATIVE
 ADVISED THAT WAS THEIR INTENTION. TO INCREASE THE ? IN.
 DOMESTIC METER TO 1.5 IN., THE SMALL SERVICE LINE WOULD
 HAVE TO BE REPLACED WITH A 2 IN. SERVICE LINE PER WATER
 SERVICE STANDARD DETAILS AND APPROVED MATERIAL LIST.
 -THE EXISTING PVB BACKFLOW ASSEMBLY FOR THE EXISTING
 PARKS IRRIGATION METER IS THEIR PROPERTY. APPROVAL
 WOULD NEED TO BE OBTAINED PARKS REPRESENTATIVES TO
 REMOVE IT. THE ASSEMBLY COULD NOT BE RELOCATED AND
 REUSED AS A CONTAINMENT BACKFLOW ASSEMBLY IN OUR WATER
 SERVICE AREA.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 DIRECT: (561) 494-1098 [email protected]
  