| Date |
Text |
| 2020-07-07 15:41:07 | 1. PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND |
| | INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER |
| | (Z-XXXXXXXX). |
| | 2. THE CITY OF WEST PALM BEACH HAS A NUMBER OF |
| | REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY |
| | AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND |
| | WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE |
| | DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK |
| | BELOW: |
| | HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WPB_W |
| | EBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FULL-P |
| | ACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97B19 |
| | 60045731D3658206F27451722716EF |
| | THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE |
| | FOUND HERE: |
| | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR |
| | MS,-PERMITS-APPLICATIONS |
| | ALSO SEE: CODE OF ORDINANCES, CITY OF WEST PALM BEACH, |
| | FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED |
| | SEPT. 22, 2008. (SUPPLEMENT NO. 18) |
| | CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL, |
| | SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER |
| | SERVICE FACILITIES OF THE CITY. |
| | 3. THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE |
| | CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY |
| | BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS, |
| | BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION. |
| | 4. PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY |
| | OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC |
| | RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF |
| | YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE |
| | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL |
| | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT |
| | [email protected] OR 561-494-1079 FOR FURTHER |
| | ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION |
| | ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD |
| | SURVEY, POT-HOLING, SOFT DIGS ETC. |
| | 5. AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH |
| | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, |
| | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR |
| | MORE INFORMATION, REFER TO THE LINK BELOW: |
| | HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI |
| | CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL |
| | 6. PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS |
| | OF ALL WATER, STORM WATER, AND SANITARY AND SEWER |
| | LINES, INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER |
| | AND SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES, |
| | METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE |
| | SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING |
| | GRADES, PIPES SIZES, MATERIALS, ELEVATIONS, |
| | ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL |
| | INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER |
| | LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE |
| | PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN |
| | VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS. |
| | ADDITIONALLY, PLAN VIEW SHALL SHOW ALL EXISTING AND |
| | PROPOSED UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER |
| | OPTIC, ELECTRIC, GAS, AND CABLEVISION & |
| | TELECOMMUNICATION FACILITIES LOCATED ON THE |
| | RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL |
| | UTILITY CROSSINGS. CUT AND CAP UTILITIES NOT IN USE, |
| | AND REMOVE ANY ABANDONED UTILITY LINES LARGER THAN 2 |
| | INCHES FROM CITY RIGHT OF WAY. |
| | 7. PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE |
| | DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB |
| | DEVELOPMENT APPLICATION). |
| | 8. WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY |
| | SHALL BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND |
| | SPECIFY PROPOSED LENGTH IN FEET. |
| | 9. PLEASE COORDINATE PLACEMENT OF WATER METERS/BACKFLOW |
| | PREVENTION ETC. WITH MARK HURLEY OF PUBLIC UTILITIES |
| | CUSTOMER SERVICE AT 561-822-2262 OR [email protected]. |
| | 10. PLEASE CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA |
| | AND FIRE BACKFLOW PREVENTER AS DCDA. |
| | 11. PLEASE PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED |
| | LOCATION OF WATER METER AND BACKFLOW PREVENTION. |
| | 12. PROVIDE VERTICAL DATUM AND DATUM CONVERSION |
| | INFORMATION (NAVD 1988 AND NGVD 1929). |
| | 13. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND |
| | PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM |
| | AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE |
| | PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER. |
| | 14. PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND |
| | STORMWATER INFRASTRUCTURE ALONG ENTIRE PROJECT |
| | FRONTAGE. |
| | 15. CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY |
| | SEWER ARE REQUIRED. |
| | 16. PLEASE PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE |
| | ONSITE JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY |
| | 75 FEET. |
| | 17. FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND |
| | NPDES NOI REQUIREMENTS WILL BE ENFORCED. |
| | - AN NOI IS REQUIRED FOR PROJECTS THAT: |
| | - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS |
| | THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF |
| | DEVELOPMENT OR SALE; |
| | - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE |
| | STATE OR TO SURFACE WATERS OF THE STATE THROUGH A |
| | MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4). |
| | - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF |
| | CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION |
| | THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL |
| | SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT |
| | OF THE 10-2 CERTIFICATION. |
| | 18. FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE |
| | EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS. |
| | 19. FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES |
| | OF WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS. |
| | 20. FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING |
| | APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT |
| | SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING |
| | SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED |
| | LEAD-FREE DESIGN. |
| | 21. FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY LINES |
| | ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY |
| | LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT |
| | PARCELS. |
| | 22. FOR FORMAL ENGINEERING SUBMITTAL, IF WATER LINES |
| | ARE BEING REPLACED IN ROW, SHOW ADJACENT PARCEL |
| | ADDRESSES. |
| | 23. FOR FORMAL ENGINEERING SUBMITTAL, ADD NOTE TO |
| | PROVIDE 50 FT. PAVEMENT RESTORATION TRANSITION ON EACH |
| | SIDE OF PROPOSED TRENCH IN CITY MAINTAINED ROADWAY |
| | AREAS PER CITY OF WPB STANDARD DETAIL GC-8. |
| | 24. FOR FORMAL ENGINEERING SUBMITTAL, SHOW DIMENSIONS |
| | OF PROPOSED DUMPSTER PER CURRENT CITY OF WPB STANDARD |
| | DETAIL GC-7. |
| | 25. FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE |
| | CALCULATIONS OF PERVIOUS AND IMPERVIOUS AREAS FOR |
| | PROPOSED IMPROVED AREAS. |
| | |
| | THE FOLLOWING COMMENTS ARE FROM HONG XU, PROJECT |
| | ENGINEER, PUBLIC UTILITIES, 561-494-1047, [email protected]: |
| | |
| | NEED TO SHOW WATER SERVICE AND SANITARY SEWER LATERAL |
| | CONNECTIONS ON THE PLAN. IT SAYS SEE PLUMBING PLANS FOR |
| | CONNECTIONS. BUT THE PLUMBING PLANS ARE NOT PROVIDED IN |
| | THE SUBMITTAL. |
| | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR |
| | CONCERNS, THANKS. |
| | |
| | ADDITIONAL COMMENTS ADDED JULY 13, 2020 FROM MARK |
| | HURLEY, CUSTOMER SERVICE SUPERVISOR, CITY OF WPB PUBLIC |
| | UTILITIES, [email protected], 561-822-2262: |
| | |
| | -THE OLD METER FOR THE PROPERTY IS 3/4 IN. AND ACCOUNT |
| | IS NOT ACTIVE. PLAN DESIGNER WOULD NEED TO DETERMINE IF |
| | THE 3/4 IN. METER WILL BE SUFFICIENT FOR THE WATER |
| | DEMAND OR IF IT NEEDS TO BE UPSIZED TO 1 IN. METER. |
| | WILL HAVE TO WORK WITH OUR UTILITY BILLING DEPT TO |
| | DETERMINE THE COSTS INVOLVED EITHER WAY. |
| | -PLEASE ADD WATER DEMAND CALCULATIONS TO PLAN. |
| | -THE 2 IN. LINE CURRENTLY HAS A 1.5 IN. METER. IT LOOKS |
| | TO BE AN ACTIVE PARKS IRRIGATION METER. WE WOULD HAVE |
| | TO VERIFY WITH PARKS IF THEY ARE USING IT AND WHAT IT |
| | SERVES (MAY WATER THE ROW GRASS). IF IT IS NOT |
| | AVAILABLE, THEN MAY HAVE TO GET NEW LINE, TAP, & METER. |
| | IF AVAILABLE PLAN DESIGNER WOULD NEED TO DETERMINE IF |
| | 1.5 IN. METER IS SUFFICIENT FOR DEMAND OR IF NEED |
| | UPSIZE TO 2 IN. METER. SAME WITH UTILITY BILLING. |
| | -PLAN DRAWINGS FOR THE WATER LINES DO NOT MATCH THE |
| | HISTORIC DRAWINGS WITH THE 4 IN. WATER MAIN BRANCH |
| | ACROSS 15TH ST AND E-W SERVICE LINES. THEY NEED TO BE |
| | VERIFIED IN THE FIELD AND PLAN UPDATED AS NEEDED. |
| | -PLEASE REFERENCE THE WS STANDARD DETAILS FOR THE |
| | BACKFLOW ASSEMBLIES AND USE RP TYPE ASSEMBLIES. |
| | DEPENDING ON METHOD, MAY HAVE TO BORE UNDER SIDEWALK OR |
| | CUT IT OUT TO PLACE NEW PIPING AND SLEEVE UNDER |
| | SIDEWALK. |
| | -LOOKS LIKE NEW HYDRANT BEING INSTALLED NEAR NW CORNER |
| | OF PROPERTY. NEED LABEL TO MAKE THAT MORE CLEAR AND THE |
| | TEE DOES NOT LOOK LIKE IT IS DRAWN ONTO THE CORRECT |
| | PIPING. PLEASE ALSO MOVE VALVE IN SIDEWALK EAST OUT OF |
| | THE SIDEWALK. |
| | |
| | |
| | RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR, WEST PALM BEACH, FL |
| | 33401 |
| | DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE: |
| | (561) 246-9525 |
| | EMAIL: [email protected] |
| | WWW.WPB.ORG/ENGINEERING |
| | |
| |