Plan Review Notes
Plan Review Notes For Project Z20060013
Project Number Z20060013
Review Stop STORM
Sequence Number 2
Notes
Date Text
2020-11-24 12:31:28THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 10/19/20 SUBMITTAL PACKAGE.
  
 1. SURVEY INDICATES PAR TOF THE SITE IS WITHIN A
 SPECIAL FLOOD HAZARD AREA (SFHA). FINISHED FLOORS AND
 MECHANICAL EQUIPMENT WILL BE REQUIRED TO BE A MINIMUM
 OF 2 FEET ABOVE THE BASE FLOOD ELEVATION OF THE SFHA.
  
 2. THE CITY'S OFFICIAL VERTICAL DATUM IS NGVD1929. THE
 CITY HAS ALLOWED THE USE OF NAVD1988 PROVIDED THE
 RELATIONSHIP BETWEEN NGVD1929 AND NAVD1988 IS PROVIDED.
 EVERY SHEET WITH ELEVATION INFORMATION WILL NEED TO
 LIST THE VERTICAL DATUM AND CONVERSION EQUATION TO
 NGVD1929.
  
 3. NO ENGINEERING PLANS WERE INCLUDED WITH THIS
 SUBMITTAL. THE ARCHITECTURAL SITE PLAN (SP1.1)
 INDICATES THE OVERFLOW BULLPEN PARKING LOT WILL BE
 PAVED.
  
 4. ADJUSTMENTS TO THE SOTRMWATER DETENTION STORAGE AREA
 WILL BE REQIRED IF THE IMPERVIOUS/PERVIOUS AREA RATIO
 OF THE BULLPEN PARKING AREA IS GREATER THAN WHAT IS
 LISTED IN EXISTING SFWMD ERP PERMIT.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  