2021-05-06 12:27:02COMMENTS PER RICK ROSSANO, PROJ. COORD. WPB ENG.
 SERVICES, [email protected], 561-494-1098:
  
 1. THE CITY OF WEST PALM BEACH HAS A NUMBER OF
 REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY
 AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND
 WASTEWATER UTILITIES WITHIN THE CITY. TO VIEW
 DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AND OTHER
 ENGINEERING RELATED DOCUMENTS, CLICK HERE OR GO TO: HTT
 PS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING/ENGINEERING-FOR
 MS-PERMITS-AND-APPLICATIONS .
 2. CODE OF ORDINANCES, CITY OF WEST PALM BEACH,
 FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED
 SEPT. 22, 2008. (SUPPLEMENT NO. 18) CHAPTER 90
 UTILITIES, ARTICLE I. SEC. 90-7.
 POLICY REGARDING EXTENSION OF WATER OR SEWER SERVICE
 FACILITIES OF THE CITY:
 THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
 3. AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, CLICK HERE OR GO TO: HTTPS://WWW.WPB.
 ORG/GOVERNMENT/ENGINEERING/ENGINEERING-FORMS-PERMITS-AN
 D-APPLICATIONS .
 4. PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1040 FOR FURTHER
 ASSISTANCE.
 5. PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS
 OF ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES,
 INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND
 SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES,
 METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE
 SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING
 GRADES, PIPES SIZES, MATERIALS, ELEVATIONS,
 ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL
 INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER
 LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN
 VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
 PLEASE SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL. ADDITIONALLY, PLAN VIEW SHALL SHOW ALL
 EXISTING AND PROPOSED UNDERGROUND UTILITY LAYOUT,
 INCLUDING FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED ON THE
 RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL
 UTILITY CROSSINGS.
 6. CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 ROW.
 7. PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE
 DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB
 DEVELOPMENT APPLICATION).
 8. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND
 PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM
 AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE
 PER FAC 64E-8 FOR WATER AND PER FAC 64-E.008 FOR SEWER.
 9. SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION
 (NAVD 88 AND NGVD 29).
 10. PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND
 STORMWATER ALONG ENTIRE PROJECT FRONTAGE.
 11. PLEASE ADD NOTE TO PLANS SPECIFYING CITY?S
 DOWNSTREAM LIFT STATION NUMBER.
 12. PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
 13. PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR
 PROPOSED SANITARY LATERALS.
 14. PLEASE LABEL WATER LINES AS PRIVATE WHERE
 APPLICABLE.
 15. PLEASE PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED
 LOCATION OF WATER METER AND BACKFLOW PREVENTION.
 16. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING
 PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT
 HIM AT 561-494-2262 OR [email protected]
 17. PROVIDE DEDICATED UTILITY EASEMENTS TO ALLOW ACCESS
 FOR CITY PERSONNEL TO PROPOSED UTILITY WATER METERS.
  
 FOLLOWING COMMENTS FROM MARK HURLEY, FIELD CUSTOMER
 SERVICE SUPERVISOR, CITY OF WEST PALM BEACH PUBLIC
 UTILITIES, 561-822-2262 [email protected]
  
 BANYAN VIEW:
  
 -LANDSCAPE PLAN DOES NOT APPEAR TO BE DESIGNED WITH
 REGARD TO WATER METER AND BACKFLOW ASSEMBLY LAYOUT.
 SHOWS THEM POSITIONED DIFFERENTLY. PLEASE MAKE SURE
 LANDSCAPE PLANS SHOWS THEIR POSITIONING ACCURATELY, AND
 LANDSCAPING AND WATER UTILITIES DO NOT CONFLICT.
  
 -WATER PLAN SHOWS UTILITY MARKED IRR RUNNING ACROSS THE
 SOUTHEAST AREA OF THE PROPERTY, AND THEN UP AND ACROSS
 THE ROAD. PLEASE VERIFY THAT IT IS ACCURATELY SHOWN AND
 PRIVATELY OWNED.
  
 -ON WATER PLAN THERE IS A SMALL SYMBOL THAT LOOKS LIKE
 A BOX WITH A ?T? IN IT IN THE MIDDLE OF THE SIDEWALK
 NEAR THE STREET CROSSING. PLEASE IDENTIFY WHAT IT IS.
  
 -CIVIL PLANS ARE NOT ACCURATELY SHOWING THE EXISTING
 WATER METER BOX IN THE SIDEWALK JUST A FEW FEET WEST OF
 THE EXISTING DRIVEWAY. PLEASE SHOW AND ADD LABEL METER
 BOX AND WATER SERVICE WITH WHAT IS HAPPENING TO THEM.
 IT APPEARS THE CURRENT ACCOUNT HOLDER IS BANYAN CAY
 GOLF CLUB LLC.
  
 -CANNOT FIND PROPERTY ADDRESS ON CIVIL PLANS.
  
  
 BANYAN CAY RESIDENTIAL AREA:
  
 -THERE IS STILL A WATER SERVICE ISSUE THAT I DO NOT
 BELIEVE HAS BEEN RESOLVED WITH THE ISLAND AT THE
 ROUNDABOUT OF BANYAN CAY DRIVE. PLEASE PROVIDE CONTACT
 INFORMATION FOR PERSONS WITH KNOWLEDGE OF CONSTRUCTION
 AND RESPONSIBLE FOR THE LANDSCAPE ISLAND.
  
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  