Plan Review Notes
Plan Review Notes For Project Z20050013
Project Number Z20050013
Review Stop SURVEY
Sequence Number 2
Notes
Date Text
2020-09-02 12:09:421. 8" WATER MAIN APPEARS TO END AT LABEL OF
 PRESIDENTIAL WAY.
 2. NO TIE-IN TO EXISTING WATER MAIN SHOWN.
 3. NEED ENLARGEMENT OF METER AND BACK-FLOW AREA.
 4. PLAN NEEDS TO BE SPLIT INTO SEPARATE PAVING AND
 GRADING; WATER AND SEWER.
 5. IF CITY ABANDONS THE DRAINAGE EASEMENT, A
 REPLACEMENT DE WILL NEED TO BE DEDICATED TO THE POA.