Plan Review Notes
Plan Review Notes For Project Z20050013
Project Number Z20050013
Review Stop STORM
Sequence Number 2
Notes
Date Text
2020-09-21 23:58:05THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 8/26/2020 SUBMITTAL PACKAGE:
  
 1. CROSS SECTION A-A INDICATES THE RETAINING WALL AT
 THE PROPERTY LINE WILL VARY FROM 0' TO 8' IN HEIGHT
 ABOVE ADJACENT GRADE. THE CONCEPTUAL ENGINEERING PLAN
 DOES NOT PROVIDE A PROPOSED GRADING PLAN TO COMFIRM THE
 NEED FOR THE RETAINING WALL.
  
 2. IF THE RETAINIANGE WALL IS NEEDED, IT SHALL BE
 DESIGNED SO AS TO NOT ENCROACH ONTO ADJACENT PROPERTY
 INCLUDING ANY FOOTER.
  
 3. STAFF IS CONCERED THERE MAY BE 8 FEET OF FILL ADDED
 IN THE DRAINAGE EASEMENT.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]