| Plan Review Notes For Project Z20050013 |
| Project Number |
Z20050013 |
|
| Review Stop |
STORM |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-09-21 23:58:05 | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE | | | 8/26/2020 SUBMITTAL PACKAGE: | | | | | | 1. CROSS SECTION A-A INDICATES THE RETAINING WALL AT | | | THE PROPERTY LINE WILL VARY FROM 0' TO 8' IN HEIGHT | | | ABOVE ADJACENT GRADE. THE CONCEPTUAL ENGINEERING PLAN | | | DOES NOT PROVIDE A PROPOSED GRADING PLAN TO COMFIRM THE | | | NEED FOR THE RETAINING WALL. | | | | | | 2. IF THE RETAINIANGE WALL IS NEEDED, IT SHALL BE | | | DESIGNED SO AS TO NOT ENCROACH ONTO ADJACENT PROPERTY | | | INCLUDING ANY FOOTER. | | | | | | 3. STAFF IS CONCERED THERE MAY BE 8 FEET OF FILL ADDED | | | IN THE DRAINAGE EASEMENT. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | 561-351-0510 (M) | | | [email protected] |
| |