2020-06-10 18:58:17DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. ACCESSIBLE ROUTE FROM PUBLIC RIGHT-OF-WAY. SITE
 PLAN, SHEET SP-1, DOES NOT SHOW A WHEELCHAIR ACCESSIBLE
 ROUTE WHICH DOES NOT REQUIRE THE WHEELCHAIR USER TO
 TRAVEL ALONG THE DRIVE LANES AND/OR PASS BEHIND PARKED
 VEHICLES IN ORDER TO GET FROM THE PUBLIC RIGHT-OF-WAY
 TO THE BUILDING B LOBBY ENTRANCE. WHEN SUBMITTED FOR
 PERMIT, THE PLANS SHALL SHOW AT LEAST ONE ACCESSIBLE
 ROUTE, COMPLYING WITH FAIR HOUSING ACT/SECTIONS 206.2
 AND 402.2 OF FLORIDA ACCESSIBILITY CODE, FROM THE
 PUBLIC RIGHT-OF-WAY TO ALL ACCESSIBLE BUILDING OR
 FACILITY ENTRANCES.
  
 3. ACCESSIBLE ROUTE BETWEEN BUILDINGS. SITE PLAN, SHEET
 SP-1, DOES NOT SHOW A WHEELCHAIR ACCESSIBLE ROUTE WHICH
 DOES NOT REQUIRE THE WHEELCHAIR USER TO TRAVEL ALONG
 THE DRIVE LANES AND/OR PASS BEHIND PARKED VEHICLES IN
 ORDER TO GET FROM BUILDING A TO THE BUILDING B LOBBY
 ENTRANCE. WHEN SUBMITTED FOR PERMIT, SHOW AT LEAST ONE
 ACCESSIBLE ROUTE, COMPLYING WITH FAIR HOUSING
 ACT/SECTIONS 206.2 AND 402.2 OF FLORIDA ACCESSIBILITY
 CODE, CONNECTING ACCESSIBLE BUILDING OR FACILITY
 ENTRANCES WITH ALL ACCESSIBLE SPACES AND ELEMENTS
 WITHIN THE BUILDING OR FACILITY.
  
 4. LOCATION OF ACCESSIBLE PARKING SPACES. SITE PLAN,
 SHEET SP-1, SITE DATA TABLE SHOWS THAT 9 ACCESSIBLE
 PARKING SPACES WILL BE PROVIDED. THE PLAN SHOWS 6 OF
 THOSE ACCESSIBLE PARKING SPACE LOCATED NEAR THE
 ENTRANCE OF BUILDING B (FOR 77 RESIDENTIAL UNITS) BUT
 ONLY 3 OF THE ACCESSIBLE PARKING SPACES ARE SHOWN
 LOCATED NEAR THE ENTRANCE OF BUILIDNG A (FOR 120
 RESIDENTIAL UNITS) EVEN THOUGH BUILDING A HAS 43
 ADDITIONAL RESIDENTIAL UNITS AND IS WHERE THE LEASING
 OFFICE, CLUB LOUNGE, FITNESS ROOM AND SWIMMING POOL ARE
 LOCATED. MUST PROVIDE ENOUGH ACCESSIBLE PARKING SPACES
 NEAR THE ENTRANCE TO BUILDING A. PER FAIR HOUSING
 ACT/SECTION 208.3 OF FLORIDA ACCESSIBILITY CODE,
 ACCESSIBLE PARKING SPACES ARE TO BE LOCATED ON THE
 SHORTEST POSSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING
 TO AN ACCESSIBLE ENTRANCE AND DISPERSED ACCORDING TO
 NEED.
  
 5. VAN ACCESSIBLE PARKING SPACES. THE ACCESSIBLE
 PARKING AT BUILDING B INCLUDES PARKING SPACES UNDER THE
 BUILIDING, BUT NONE ARE MARKED AS VAN ACCESSIBLE. PER
 FAIR HOUSING ACT/SECTION 208.2.4 OF FLORIDA
 ACCESSIBILITY CODE, ONE IN EVERY SIX REQUIRED
 ACCESSIBLE SPACES (AT LEAST ONE) IN A PARKING
 STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND DESIGNED IN
 ACCORDANCE WITH SECTION OF 502 OF FLORIDA ACCESSIBILITY
 CODE (VERTICAL CLEARANCE NOT LESS THAN 98 INCHES AT
 SPACE AND VEHICULAR ACCESS ROUTE).
  
 6. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 7. EMERGENCY EGRESS FROM LEVEL 2 OF BUILDING A.
 BUILDING A FLOOR PLAN SHEET A1-01A SHOWS TWO EGRESS
 STAIRS. LEVEL 2 RESIDENTS WOULD HAVE TO GO THROUGH THE
 "2 STORY LEASING/CLUB/FITNESS" AREA TO GET TO THE NORTH
 STAIR. IF THAT AREA IS A DOULDE STORY HEIGHT SPACE THAT
 WILL NOT WORK, AND ANOTHER STAIR WOULD BE REQUIRED. IF
 THE "LEASING/CLUB/FITNES" AREA DOES HAVE A 2ND LEVEL,
 THE RESIDENTS WOULD HAVE TO GO THROUGH DOORS THAT ARE
 SHOWN TO SWING IN THE WRONG DIRECTION FOR NORTHWARD
 EGRESS, ANY ACCESS CONTROL ON THOSE DOES MUST ALLOW
 EGRESS UNDER ALL CONDITIONS, AND THE INTERIOR
 CONGURATION OF THE SPACE MUST BE SHOWN AS THE LAYOUT IS
 NOT CURRENTLY SHOWN. PER SECTION 1006.3.1 AND 1010.1.9
 OF FLORIDA BUILDING CODE, TWO MEANS OF EGRESS ARE
 REQUIRED AND EGRESS DOORS SHALL BE READILY OPENABLE
 FROM THE EGRESS SIDE..
  
 8. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 9. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
 10. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT
 CAROLINE PUELL, ADDRESSING COORDINATOR, AT (561) 805
 6659, OR BY EMAIL: [email protected]
  
 11. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT
 TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE
 ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP
 ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  
  Print


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved