| Plan Review Notes For Project Z20040025 |
| Project Number |
Z20040025 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-05-18 14:31:28 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. | | | | | | 2. THE WEST ELEVATION OF THE LEWIS HALL WEST BUILDING | | | HAS WINDOW OPENINGS, LOUVERS AND WALL-MOUNTED AIR | | | CONDITIONING UNITS. THOSE ARE CONSIDERED AS UNPROTECTED | | | OPENINGS AND, PER SECTION 705.8.1 OF FLORIDA BUILDING | | | CODE, THE EXTERIOR WALL MUST BE AT LEAST 3 FEET FROM | | | THE PROPERTY LINE, AND THE AREA OF THOSE OPENINGS IN | | | ANY STORY MUST BE NO MORE THAN 15% OF THE WALL AREA OF | | | THAT STORY. COMPLIANCE CANNOT BE ASSESSED BECAUSE NO | | | DIMENSIONED SITE PLAN HAS BEEN PROVIDED TO SHOW THAT | | | THE WEST ELEVATION OF THE LEWIS HALL WEST BUILDING WILL | | | BE AT LEAST 3 FEET FROM THE PROPERTY LINE, AND NO | | | CALCULATIONS HAVE BEEN PROVIDED TO SHOW THAT THE AREA | | | OF THE OPENINGS IN THE FIRST AND SECOND STORIES OF THE | | | WALL IS LESS THAN 15% OF THE WALL AREA OF THAT STORY. | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
| |