Plan Review Notes
Plan Review Notes For Project Z20040015
Project Number Z20040015
Review Stop ENG - PPRC
Sequence Number 4
Notes
Date Text
2022-03-03 07:30:56Z20040015 - IMECA HARDWARE, 3200 45TH ST. ? RESUB ?
 3-1-22
  
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPT., DIRECT: (561) 494-1098 [email protected]
  
 PASS WITH PROVISO:
  
 1. PAVEMENT RESTORATION NOTE WOULD APPLY TO WORK IN
 ROADWAY. FOR SIDEWALK RESTORATION, PLEASE REFER TO CITY
 STANDARD DETAIL GC-1 AND UPDATE NOTE ON PLANS.
  
  
 MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR;
 561-822-2262 [email protected]
 1. WITH RESPECT TO FIRELINE SIZING, PLAN SHEETS DO NOT
 ALL MATCH. SOME SAY 4 INCH FIRELINE AND PIPING AND
 OTHERS SAY 6 INCH. PLEASE MAKE SURE ALL PLANS MATCH.
 DCDA SHOULD BE SAME SIZING AS UPSTREAM SERVICE PIPING.
 2. ON LANDSCAPING PLAN A BUSH APPEARS TO BE PLANTED ON
 PROPOSED WATER METER BOX.
 3. LANDSCAPING PLAN DOES NOT SHOW THE FDC AND CONCRETE
 POLE NEAR NORTHWEST AREA OF PROPERTY.
 4. LANDSCAPING PLAN SHOWS 2 HORSE PUMP STATION AT WEST
 SIDE OF PROPOSED BUILDING. PLEASE DESCRIBE WHAT IT IS
 USED FOR.
 5. BELIEVE THAT A BUILDING IS BEING DEMOLISHED, BUT DID
 NOT SEE A DEMO PLAN. PLEASE INCLUDE DEMO PLAN WITH
 CIVIL PLAN SET AT FORMAL ENGINEERING SUBMITTAL
  