| 2021-09-27 16:53:58 | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE | | | 9-8-2021 SUBMITTAL PACKAGE. | | | | | | 1. WHAT IS THE VERTICAL CLEARANCE BETWEEN THE 15" STORM | | | OUTFALL PIPE AND 8" ROOF DRAIN PIPE AS THEY CROSS THE | | | 6" WASTEWATER LINE, 4" FIRE LINE AND 1" WATER LINE. | | | LABEL THESE VERTICAL CLEARANCES ON THE UTILITY PLAN AND | | | UTILITY CONNECTION PROFILE ON SHEET C-11. | | | | | | 2. NORTH ARROW POINTING TO THE WEST ON SHEET C-11. | | | | | | 3. SITE LIGHT FIXTURE IS LOCATED WITHIN THE 2-FOOT | | | OVERHANG OF THE PARKING STALLS ON THE WEST SIDE OF THE | | | SITE. | | | | | | 4. WHEEL STOPS MAY NOT BE NEEDED IF THERE IS TYPE 'D' | | | CURB AT THE END OF THE PARKING STALL AND THE PARKING | | | STALL INCLUDES 2 FEET OF OVERHANG OVER THE SIDEWALK OF | | | LANDSCAPE STRIP. IF WHEEL STOPS ARE USED MAKE SURE THE | | | PARKING SPACES ARE DEEP ENOUGH SO THAT THE STANDARD CAR | | | DOES NOT STICK OUT INTO THE DRIVE LANE. | | | | | | 5. CHECK COVER DEPTH OVER THE PROPOSED STORM PIPES IN | | | THE PARKING LOT. | | | | | | 6. CHECK THE THICKNESS OF THE CONCRETE ABOVE THE WEIR | | | OPENING IN THE CONTROL STRUCTURE. IS THE GRATE | | | SUPPORTED ON THIS SIDE? | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | 561-351-0510 (M) | | | [email protected] | | | |
| |