2020-09-21 22:55:26THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 9/11/2020 ROUTED SUBMITTAL PACKAGE.
  
 1. DRAINAGE CALCULATIONS:
 A. REVIEW VALUE OF H2 IN THE EXFILTRATION CALCULATIONS
  
 B. REVIEW LENGTH OF 6-INCH PIPE IN THE CASCADE MODEL
 AND THE LENGTH LISTED ON THE PGD PLANS.
  
 C. THE PROPOSED DRAINAGE AREA DOES NOT EQUAL THE
 EXISTING DRAINAGE AREA.
  
 2. SHOW THE PROPER WIDTH OF PAVEMENT MILL AND OVERLAY
 (50 FEET EACH SIDE OF TRENCH CUT) ON PARKER AVE. MILL
 AND OVERLAY LIMITS TO INCLUDE COMPLETE TRAVEL LANE.
  
 3. PROVIDE TOPOGRAPHIC SURVEY OF AVAILABLE.
  
 4. 6" HDPE PIPE WILL ONLY HAVE LESS THAN 6" OF COVER
 WHERE IT CROSSES THE DRIVEWAY.
  
 5. ADD WEST INVERT ELEVATION FOR STRUCTURE S-3.
  
 6. SEE STALL PAINTING DETAIL IN SECTION 94-485.J OF THE
 ZONING AND LAND DEVELOPMENT CODE.
  