2020-09-22 00:36:09THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 8/27/2020 ROUTED SUBMITTAL PACKAGE.
  
 1. A SEPARRATE CONTROL STRUCTION WILL BE NEEDED FOR THE
 STORMWATER MANAGEMENT SYSTEM.
  
 2. MOVE THE EXFILTRATION TRENCH CLOSER TO WHERE THE
 CONTROL STRUCTURE WILL BE.
 A. CAN THE EXFILTRATION TRENCH SHOWN BETWEEN STRUCTURES
 2 AND 3 BE MOVED TO BETWEEN STRUCTURES 9 AND 10 AND THE
 PIPE BETWEEN STRUCTURES 2 AND 3 BE ELIMINATED?
 B. CAN SOME OF THE EXFILTRATION TRENCH BETWEEN
 STRUCTURES 2 AND 11 BE MOVED TO BETWEEN STRUCTURES 7
 AND 8 AND/OR BETWEEN STRUCTURES 8 AND 9.
  
 3. LABEL WHICH STORM INVERTS ARE TO BE COVERED BY A
 PRB.
  
 4. DRAINAGE SYSTEM SHOWN ON THE UTILITY PLAN DOES NOT
 MATCH WHAT IS SHOWN ON THE PGD PLAN.
  
 5. SHOW MILL AND RE-SURFACE LIMITS ON THE UTILITY PLAN
 FOR THE TRANCH CUTS ON 13TH ST.
  
 6. PROVIDE SHEET 1 OF 2 OF THE SURVEY.
  