| Plan Review Notes For Project Z20030013 |
| Project Number |
Z20030013 |
|
| Review Stop |
ENG - PPRC |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-08-17 15:23:48 | COMMENTS PER MARK HURLEY, CITY OF WPB PUB. UTIL. CUST. | | | SERVICE, [email protected], OR 561-822-2262: | | | | | | -THERE IS A BACKFLOW ASSEMBLY MISSING FROM THE WATER | | | ENGINEERING PLAN. PLEASE ADD IT. | | | -DCDA BACKFLOW ASSEMBLY SHOULD NOT BE ATTACHED TO THE | | | NORTHERN METER BOX. THAT LARGE FIRELINE SHOULD BE A | | | SEPARATE WATER SERVICE TO THE WATER MAIN. PLEASE | | | CORRECT. | | | -PLEASE ADD ROOT BARRIERS BETWEEN THE TREES AND | | | CUSTOMER?S FIRELINE PIPING AFTER DCDA. | | | -ON FORMAL ENGINEERING SUBMITTAL, LABEL THE SIZES OF | | | THE WATER METERS AND BACKFLOW ASSEMBLIES. THE PRIVATE | | | DOMESTIC WATER PIPE SAYS 3 IN., BUT THE DOMESTIC METER | | | AND BACKFLOW ASSEMBLY IS SMALLER THAN THAT. IF LARGER | | | METER IS NEEDED, NEW WATER SERVICE MAY NEED TO BE | | | BUILT. LARGER METER MAY REQUIRE MORE SPACE, | | | ABOVE-GROUND INSTALLATION, AND UTILITY EASEMENTS. | | | -FOR ENGINEERING SUBMITTAL, IDENTIFY EXISTING PRIVATE | | | FIRELINE PIPING AND WHAT WILL BE HAPPENING TO IT. WILL | | | IT BE ABANDONED IN PLACE, REMOVED, OR GROUTED? | | | |
| |