Plan Review Notes
Plan Review Notes For Project Z20030013
Project Number Z20030013
Review Stop ENG - PPRC
Sequence Number 2
Notes
Date Text
2020-08-17 15:23:48COMMENTS PER MARK HURLEY, CITY OF WPB PUB. UTIL. CUST.
 SERVICE, [email protected], OR 561-822-2262:
  
 -THERE IS A BACKFLOW ASSEMBLY MISSING FROM THE WATER
 ENGINEERING PLAN. PLEASE ADD IT.
 -DCDA BACKFLOW ASSEMBLY SHOULD NOT BE ATTACHED TO THE
 NORTHERN METER BOX. THAT LARGE FIRELINE SHOULD BE A
 SEPARATE WATER SERVICE TO THE WATER MAIN. PLEASE
 CORRECT.
 -PLEASE ADD ROOT BARRIERS BETWEEN THE TREES AND
 CUSTOMER?S FIRELINE PIPING AFTER DCDA.
 -ON FORMAL ENGINEERING SUBMITTAL, LABEL THE SIZES OF
 THE WATER METERS AND BACKFLOW ASSEMBLIES. THE PRIVATE
 DOMESTIC WATER PIPE SAYS 3 IN., BUT THE DOMESTIC METER
 AND BACKFLOW ASSEMBLY IS SMALLER THAN THAT. IF LARGER
 METER IS NEEDED, NEW WATER SERVICE MAY NEED TO BE
 BUILT. LARGER METER MAY REQUIRE MORE SPACE,
 ABOVE-GROUND INSTALLATION, AND UTILITY EASEMENTS.
 -FOR ENGINEERING SUBMITTAL, IDENTIFY EXISTING PRIVATE
 FIRELINE PIPING AND WHAT WILL BE HAPPENING TO IT. WILL
 IT BE ABANDONED IN PLACE, REMOVED, OR GROUTED?
  