| Date |
Text |
| 2021-09-29 12:16:55 | COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE |
| | SUPER., WPB PUBLIC UTILITIES, 561-494-2262 OR |
| | [email protected]: |
| | |
| | 4) SOME STANDARD DETAILS ARE OLD REVISION AND SOME ARE |
| | DUPLICATED. PLEASE CORRECT. |
| | |
| | RESPONSE: DETAILS WILL BE CLARIFIED |
| | |
| | NOT SATISIFIED. SOME STANDARD DETAILS ARE STILL OLD |
| | REVISION AND DUPLICATED. CAN CORRECT AT FORMAL |
| | ENGINEERING SUBMITTAL. |
| | |
| | |
| | 2) CITY WPB WATER MAINS, FORCE MAINS, FIRE HYDRANTS, |
| | WATER SERVICES AND METER BOXES SHOULD HAVE EXISTING OR |
| | PROPOSED UTILITY EASEMENTS SHOWN AND LABELED ON WATER |
| | PLAN. BACKFLOW ASSEMBLIES MAY NOT BE LOCATED IN UTILITY |
| | EASEMENTS. |
| | |
| | PROPOSED EASEMENT BOUNDARIES ARE NOT SUFFICIENT. NEED |
| | UTILITY EASEMENTS FOR ALL PROPOSED AND EXISTING CITY |
| | WPB UTILITY INFRASTRUCTURE. |
| | |
| | RESPONSE: EASEMENTS HAVE BEEN ADDED ON EXISTING AND |
| | PROPOSED MAINS. A TITLE SEARCH WILL BE DONE TO CONFIRM |
| | IF THERE ARE EXISTING EASEMENTS OVER THE EXISTING |
| | LINES. EXISTING SYSTEM APPEARS TO HAVE BEEN CONSTRUCTED |
| | IN 1990. |
| | |
| | NOT SATISIFED. SOME UTILITIES DO NOT SHOW PROPOSED |
| | EASEMENTS ON CIVIL PLANS. CAN UPDATE AT FORMAL |
| | ENGINEERING SUBMITTAL. |
| | |
| | |
| | COMMENTS FROM MICHAEL TECHNOW, PROJECT ENGINEER, WPB |
| | PUBLIC UTILITIES, 561-494-1047, [email protected] : |
| | |
| | -PLEASE REMOVE EXISTING MH AND 6? SEWER LINE. |
| | -SHOW PROFILE OF PROPOSED WATER MAIN, 1? SERVICE LINE. |
| | FROM TAP TO POINT OF SERVICE. |
| | -ADD NOTE TO ABANDON AND CAP AT MAIN FOR EXISTING |
| | SERVICES. |
| | -SHOW CLEANOUT LOCATION. |
| | -PLEASE PROVIDE POST CCTV OF SEWER LATERAL. |
| | -WHAT ARE THE ELECTRICAL BOXES FOR? |
| | -PLUG AND RESTRAIN AT PROPOSED 12? DIP. |
| | -ADD ANOTHER SAMPLE POINT AT 12?X22.15 BEND ON PROPOSED |
| | WATER MAIN. |
| | -ADD NOTE TO TIE IN AFTER FDOH RELEASE FOR USE. |
| | -DOUBLE VALVE AS REQUIRED. |
| | -SHOW EXISTING WATER SERVICE BETWEEN TIE IN AND |
| | EXISTING VALVE ON SANDHILL WAY. |
| | -THE CITY DOES NOT NEED AN EASEMENT IN ROW. |
| | -CALL OUT UTILITY CROSSINGS. |
| | |
| | |
| |
Print |