Plan Review Notes
Plan Review Notes For Project Z20020015
Project Number Z20020015
Review Stop ENG - PPRC
Sequence Number 2
Notes
Date Text
2020-08-26 14:14:22FOLLOWING COMMENTS FROM MARK HURLEY, FIELD CUSTOMER
 SERVICE SUPERVISOR
 CITY OF WEST PALM BEACH PUBLIC UTILITIES, 561-822-2262,
 [email protected]
  
 -THE EXISTING BACKFLOW ASSEMBLY IS AN OLDER MAKE/MODEL
 THAT IS NOT LEAD-FREE COMPLIANT WITH CURRENT STANDARDS.
 RECOMMEND REPLACING IT IN CONJUNCTION WITH WATER
 SERVICE STANDARD DETAIL WS-6, SINCE FOOD SERVICE IS
 PROPOSED.
  
 -IF REPLACING SIDEWALK WHERE METER BOX IS LOCATED, BE
 SURE TO USE NEW METER BOX WHEN NEW SIDEWALK IS POURED.
 BOX MUST COMPLY WITH APPROVED MATERIAL LIST AND BE
 PROPERLY ALIGNED AND WITH AT LEAST 6? THICK CONCRETE
 18? WIDE SURROUNDING IT.
  
 FOLLOWING COMMENTS ARE FROM RICK ROSSANO, PROJECT
 COORDINATOR, ENGINEERING SERVICES DEPARTMENT:
  
 1. PLEASE PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED
 LOCATION OF WATER METER AND BACKFLOW PREVENTION.
 2. PLEASE RESPOND TO ALL COMMENTS IN WRITING.
 3. PLEASE ADD DATUM CONVERSION NOTE TO ALL CONSTRUCTION
 PLAN SHEETS.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR, WEST PALM BEACH, FL
 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 DIRECT: (561) 494-1098
 MOBILE: (561) 246-9525
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING