Plan Review Notes
Plan Review Notes For Project Z20020009
Project Number Z20020009
Review Stop ENG - PPRC
Sequence Number 4
Notes
Date Text
2021-04-04 09:08:04PASSED WITH PROVISOS:
  
 -DID NOT SEE LANDSCAPING PLAN IN RESUBMITTAL DOCUMENTS
 ? PLEASE VERIFY TREES HAVE SUFFICIENT CLEARANCE
 DISTANCE FROM WATER UTILITIES.
  
 -BACKFLOW ASSEMBLIES MAY NOT BE LOCATED IN UTILITY
 EASEMENTS. THERE ARE SEVERAL CASES OF THAT CONFLICT ON
 WATER PLAN.
  
 -RELOCATION OF PROPOSED IRRIGATION METER WILL BE
 REVIEWED AT FORMAL ENGINEERING SUBMITTAL TO DETERMINE
 IF NEW TAP WILL BE REQUIRED.
  
 -DOMESTIC AND IRRIGATION METERS MAY NOT BE USED TO
 PROVIDE WATER FOR FIRE SPRINKLERS. SEPARATE DEDICATED
 FIRE SERVICE LINE WITH DETECTOR METER IS NEEDED.
  
 -FOR FORMAL ENGINEERING SUBMITTAL: 1) ADD PIPE MATERIAL
 TYPE TO LABEL FOR NEW 2 INCH WATER SERVICE. 2) ADD
 LABEL TO EXISTING WATER SERVICE FOR 1 METER WITH PIPE
 SIZE AND MATERIAL TYPE.
  
 RESPECTFULLY,
  
 MARK HURLEY
 FIELD CUSTOMER SERVICE SUPERVISOR
 CITY OF WEST PALM BEACH PUBLIC UTILITIES
 561-822-2262
  
  