| 2020-12-31 12:44:25 | 1. PLEASE ADDRESS PRIOR COMMENTS 2 THROUGH 11. |
| | 2. FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE |
| | EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS. |
| | 3. FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE |
| | ENLARGED VIEW ON PLANS OF PROPOSED LOCATION OF WATER |
| | METER AND BACKFLOW PREVENTION. |
| | 4. FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES |
| | OF WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS. |
| | 5. FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING |
| | APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT |
| | SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING |
| | SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED |
| | LEAD-FREE DESIGN. |
| | 6. FOR FORMAL ENGINEERING SUBMITTAL CLEARLY LABEL ROAD |
| | RIGHT OF WAY. |
| | 7. FOR FORMAL ENGINEERING SUBMITTAL, ADD NOTE TO |
| | PROVIDE 50 FT. PAVEMENT RESTORATION TRANSITION ON EACH |
| | SIDE OF PROPOSED TRENCH IN CITY MAINTAINED ROADWAY |
| | AREAS PER CITY OF WPB STANDARD DETAIL GC-9. |
| | 8. FOR FORMAL ENGINEERING SUBMITTAL, SHOW WATER TAP |
| | STRAIGHT ON TO PROPERTY FROM CITY WATER MAIN. |
| | 9. FOR FORMAL ENGINEERING SUBMITTAL, LIST WATER, SEWER |
| | AND FIRE FLOW DEMANDS ON DRAWINGS. |
| | 10. FOR FORMAL ENGINEERING SUBMITTAL, PLEASE SHOW BOTH |
| | EXISTING AND PROPOSED PERVIOUS AND IMPERVIOUS AREAS ON |
| | PLANS. |
| | 11. FOR FORMAL ENGINEERING SUBMITTAL, UPDATE ALL CITY |
| | OF WPB STANDARD DETAILS TO MOST CURRENT VERSIONS. |
| | 12. PLEASE RESPOND TO ALL COMMENTS IN WRITING. |
| | 13. PLEASE LABEL WATER LINES AS PRIVATE WHERE |
| | APPLICABLE. |
| | 14. PLEASE PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED |
| | LOCATION OF WATER METER AND BACKFLOW PREVENTION. |
| | 15. PLEASE UPDATE PAVEMENT RESTORATION NOTE TO COMPLY |
| | WITH CITY OF WPB STANDARD DETAIL GC-8. |
| | 16. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE |
| | SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING |
| | PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT |
| | HIM AT 561-494-2262 OR [email protected] |
| | 17. PROVIDE DEDICATED UTILITY EASEMENTS TO ALLOW ACCESS |
| | FOR CITY PERSONNEL TO PROPOSED UTILITY WATER METERS. |
| | |
| | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR |
| | CONCERNS, THANKS. RICK ROSSANO, PROJECT COORDINATOR, |
| | ENGINEERING SERVICES DEPARTMENT (561) 494-1098 |
| | [email protected] |
| | |
| | THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD |
| | CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES, |
| | PLEASE CONTACT 561-494-2262 OR [email protected]: |
| | PLEASE CONFIRM PRIOR COMMENTS WERE ADDRESSED: |
| | PROPOSED TREE INSTALLATIONS SHOULD NOT BE WITHIN 5 FEET |
| | OF WATER UTILITIES. |
| | SHEET C-1: |
| | -CANNOT HAVE WATER METER BOX OR BACKFLOW ASSEMBLY IN |
| | DRIVEWAY. METER BOX, WATER SERVICE, AND BACKFLOW |
| | ASSEMBLIES WOULD NEED TO BE RELOCATED, OR PLAN DESIGN |
| | CHANGED TO RELOCATE DRIVEWAY , IN ORDER TO ELIMINATE |
| | THAT CONFLICT. IF RELOCATING WATER SERVICE, METER BOX |
| | SHOULD NOT BE IN A SIDEWALK. |
| | -NEED LABEL SIZE OF EXISTING METER, WATER SERVICE, & |
| | BACKFLOW ASSEMBLY. |
| | -EXISTING & PROPOSED WATER MAINS, METER BOXES, AND |
| | WATER SERVICE PIPE ON PROPERTY NEEDS TO BE IN UTILITY |
| | EASEMENTS. NOT SURE IF EXISTING WATER MAINS NEAR SOUTH |
| | SIDE AND EAST SIDE ARE ALREADY IN UTILITY EASEMENTS, OR |
| | IF THOSE NEED TO BE GRANTED WITH THE PROJECT. PROPERTY |
| | OWNER SHOULD NOT BUILD WITHIN UTILITY EASEMENT. ALONG |
| | EAST SIDE OF PROPERTY, THERE IS SOME PARKING LOT AND |
| | DUMPSTER AREA STRUCTURE THAT LOOKS LIKE IT WOULD |
| | INTRUDE INTO UTILITY EASEMENT ? IF THEY ARE PROPOSED |
| | AND NOT EXISTING THEY SHOULD BE RELOCATED. |
| | -NOT SURE IF THERE IS A STREET OR ANOTHER PROPERTY |
| | ALONG SOUTH PROPERTY LINE ? CAN THAT BE ADDED? |
| | -PLAN SAYS ASPHALT TO BE REMOVED AROUND AREA FROM |
| | PROPOSED 2? METER BOX, BUT IT DOES NOT SAY THE NEW |
| | SURFACE. REQUEST NOTATION SAYING NEW MATERIAL. PREFER |
| | GRASS AROUND METER BOXES. |
| | -HARD TO DETERMINE SURFACE OVER 2? TAP. REQUEST LABEL |
| | SHOWING IF THAT IS GRASS PARKWAY OR CONCRETE SIDEWALK. |
| | -DID NOT SEE A DEDICATED FIRELINE SERVICE. WILL THE |
| | BUILDING HAVE FIRE SPRINKLERS? |
| | -DID NOT SEE A FIRE HYDRANT ADJACENT PROPERTY. IS A |
| | FIRE HYDRANT REQUIRED TO BE ADJACENT PROPERTY? |
| | -DID NOT SEE WATER DEMAND CHART ? NEED ADD IT. |
| | -RECOMMEND DUAL/PARALLEL BACKFLOW ASSEMBLIES ON |
| | DOMESTIC WATER SERVICE SO RESTAURANT HAS WATER DURING |
| | BACKFLOW MAINTENANCE OR REPAIRS. |
| | -IF EXISTING BACKFLOW ASSEMBLIES ARE RELOCATED, THEY |
| | WOULD NEED TO BE REPLACED WITH NEW LEAD-FREE COMPLIANT |
| | BACKFLOW ASSEMBLIES AND UNDERGO INSPECTION. |
| | SHEET C-4: |
| | -WATER SERVICE DETAILS ARE OLD ? SHOULD UPDATE TO |
| | NEWEST REVISION. |
| | NEW COMMENTS AS FOLLOWS: |
| | -FOR FORMAL ENGINEERING SUBMITTAL, METER BOXES ON |
| | PRIVATE PROPERTY NEED TO BE IN UTILITY EASEMENTS. |
| | SOUTHERN METER BOX MAY BE ADJUSTED SLIGHTLY SOUTH TO |
| | FALL WITHIN PROPOSED UTILITY EASEMENT. |
| | -WATER SERVICE TAP UNDER SIDEWALK WOULD LIKELY REQUIRE |
| | SIDEWALK REPLACEMENT. |
| | -DID NOT RECEIVE WRITTEN RESPONSES BACK FROM PRIOR |
| | COMMENTS IN MARCH2020. MAY HAVE ADDITIONAL COMMENTS |
| | DEPENDING ON RESPONSES. |
| | |
| |