Plan Review Notes For Project Z20020009
Project Number Z20020009
Review Stop STORM
Sequence Number 1
Notes
Date Text
2020-03-12 11:47:30THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. THE ENGINEERING AND LANDSCAPE PLANS DO NOT MATCH THE
 SITE PLAN.
  
 2. ADD FLOW ARROWS TO THE ENGINEERING PLAN TO SHOW
 SURFACE WATER RUNOFF DIRECTION.
  
 3. AVOID PUTTING UTILITIES UNDER LANDSCAPE ISLANDS.
  
 4. CONSIDER CREATING 2 FOOT OVERHANGS INTO LANDSCAPE
 AREAS FOR PARKING SPACES.
  
 5. CATCH BASIN GRATE ELEVATIONS APPEAR TO BE HIGHER
 THAN SOME ADJACENT PARKING LOT GRADES.
  
 6. THE TRAVEL LANE SPACE BETWEEN THE LANDSCAPE ISLANDS
 ON THE ENGINEERING PLAN APPEARS TO NARROW FOR TWO WAY
 TRAFFIC.
  
 7. PROVIDE BOTTOM ELEVATION OF EXISTING ONSITE DRAINAGE
 STRUCTURES THAT ARE TO REMAIN.
  
 8. CURBING NEEDED FOR NARROW PARKING AREAS NORTH OF THE
 LANDSCAPE ISLANDS.
  
 9. SHOW UTILITIES ON THE LANDSCAPE PLAN.
  
 10. SCALES SHOULD MATCH FOR SURVEY, ENGINEERING PLANS
 AND LANDSCAPE PLANS.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 3. PROVIDE A COPY OF THE SFWMD ERP PRIOR TO STARTING
 CONSTRUCTION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT