| 2020-09-11 10:29:07 | THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD |
| | CUSTOMER SERVICE SUPERVISOR, PUBLIC UTILITIES |
| | CITY OF WEST PALM BEACH ? [email protected] OR |
| | 561-822-2262 |
| | |
| | -DISCOVERED MAJOR REVISION TO WATER PLAN FROM USE OF |
| | EXISTING 3 IN. DOMESTIC WATER METER TO A 4 IN. WATER |
| | METER. THIS WOULD REQUIRE REMOVAL OF EXISTING SMALL |
| | BYPASS LINE WITH CONVERSION TO ABOVE-GROUND METER |
| | INSTALLATION (INSTEAD OF VAULT) AND FULL SIZE BYPASS. |
| | THAT EXISTING WATER SERVICE MAY ALSO BE CONFIGURED |
| | DIFFERENT THAN SHOWN ON THE PLAN ? SEE WATER SERVICE |
| | DRAWING FOR 1225 BELVEDERE RD. THE UNUSED REFERENCED |
| | WATER SERVICE STANDARD DETAILS WILL NEED BE REMOVED AND |
| | REMAINING ONES UPDATED TO SEP2019 REVISION. IF HISTORIC |
| | DRAWING FOR 1225 BELVEDERE RD WATER SERVICE IS STILL |
| | CORRECT, THEN FIRELINE POINT OF SERVICE WILL NEED BE |
| | MOVED TO THE NEXT GATE VALVE NORTH. A BRAND NEW GATE |
| | VALVE THAT ISOLATES JUST THE DOMESTIC METER (AND NOT |
| | THE FIRELINE) MUST BE LOCATED UPSTREAM OF METER. |
| | |
| | COMMENT FROM TRACY L. WARD, P.E., SENIOR STORMWATER |
| | ENG., CITY OF WPB ENG. SERVICES, 561-494-1120 / |
| | 561-351-0510, [email protected]: |
| | |
| | IF THERE IS CONSTRUCTION PROPOSED NEAR CITY MAINTAINED |
| | DRAINAGE SYSTEMS THEN THE SYSTEMS WILL NEED TO BE |
| | CCTV?D. THAT BEING SAID, BELVEDERE ROAD IS MAINTAINED |
| | BY THE COUNTY OR FDOT [SAME MAY BE TRUE FOR THE SERVICE |
| | ROAD - PLEASE CONFIRM] AND THAT ENTITY MAINTAINS THE |
| | DRAINAGE SYSTEM IN THE R/W SO NO STORM CCTV FOR THE |
| | CITY MAY BE NEEDED. |
| | COMMENT FROM RICK ROSSANO, PROJ. COORDINATOR, CITY OF |
| | WPB ENG. SERVICES, 561-494-1098, [email protected] |
| | |
| | PLEASE PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER |
| | ALONG ENTIRE PROJECT FRONTAGE. PROVISION OF CCTV IS AN |
| | ENGINEERING REQUIREMENT OF SITE PLAN APPROVAL BEFORE |
| | FORMAL ENGINEERING SUBMITTAL. |
| | |
| | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR |
| | CONCERNS, THANKS. |
| | RICK ROSSANO, PROJECT COORDINATOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | DIRECT: (561) 494-1098 [email protected] |
| | |
| |