Date Text
2020-09-11 10:29:07THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, PUBLIC UTILITIES
 CITY OF WEST PALM BEACH ? [email protected] OR
 561-822-2262
  
 -DISCOVERED MAJOR REVISION TO WATER PLAN FROM USE OF
 EXISTING 3 IN. DOMESTIC WATER METER TO A 4 IN. WATER
 METER. THIS WOULD REQUIRE REMOVAL OF EXISTING SMALL
 BYPASS LINE WITH CONVERSION TO ABOVE-GROUND METER
 INSTALLATION (INSTEAD OF VAULT) AND FULL SIZE BYPASS.
 THAT EXISTING WATER SERVICE MAY ALSO BE CONFIGURED
 DIFFERENT THAN SHOWN ON THE PLAN ? SEE WATER SERVICE
 DRAWING FOR 1225 BELVEDERE RD. THE UNUSED REFERENCED
 WATER SERVICE STANDARD DETAILS WILL NEED BE REMOVED AND
 REMAINING ONES UPDATED TO SEP2019 REVISION. IF HISTORIC
 DRAWING FOR 1225 BELVEDERE RD WATER SERVICE IS STILL
 CORRECT, THEN FIRELINE POINT OF SERVICE WILL NEED BE
 MOVED TO THE NEXT GATE VALVE NORTH. A BRAND NEW GATE
 VALVE THAT ISOLATES JUST THE DOMESTIC METER (AND NOT
 THE FIRELINE) MUST BE LOCATED UPSTREAM OF METER.
  
 COMMENT FROM TRACY L. WARD, P.E., SENIOR STORMWATER
 ENG., CITY OF WPB ENG. SERVICES, 561-494-1120 /
 561-351-0510, [email protected]:
  
 IF THERE IS CONSTRUCTION PROPOSED NEAR CITY MAINTAINED
 DRAINAGE SYSTEMS THEN THE SYSTEMS WILL NEED TO BE
 CCTV?D. THAT BEING SAID, BELVEDERE ROAD IS MAINTAINED
 BY THE COUNTY OR FDOT [SAME MAY BE TRUE FOR THE SERVICE
 ROAD - PLEASE CONFIRM] AND THAT ENTITY MAINTAINS THE
 DRAINAGE SYSTEM IN THE R/W SO NO STORM CCTV FOR THE
 CITY MAY BE NEEDED.
 COMMENT FROM RICK ROSSANO, PROJ. COORDINATOR, CITY OF
 WPB ENG. SERVICES, 561-494-1098, [email protected]
  
 PLEASE PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER
 ALONG ENTIRE PROJECT FRONTAGE. PROVISION OF CCTV IS AN
 ENGINEERING REQUIREMENT OF SITE PLAN APPROVAL BEFORE
 FORMAL ENGINEERING SUBMITTAL.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 RICK ROSSANO, PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 DIRECT: (561) 494-1098 [email protected]
  