Plan Review Notes For Project Z20010013
Project Number Z20010013
Review Stop ENG - PPRC
Sequence Number 3
Notes
Date Text
2020-07-20 07:17:16COMMENTS PER RICK ROSSANO, PROJECT COORDINATOR, CITY OF
 WPB ENG. SERVICES, [email protected] ? 561-494-1098
 CCTV OF STORMWATER IS A SITE PLAN REVIEW REQUIREMENT.
 PLEASE PROVIDE.
 COMMENTS PER MARK HURLEY, FIELD CUSTOMER SERVICE SUPV.,
 CITY OF WPB PUBLIC UTIL. [email protected] 561-822-2262
 PREVIOUS COMMENTS:
 1. RE: SHEET C-8 UTILITY EASEMENT - BACKFLOW ASSEMBLIES
 CANNOT BE IN THE UTILITY EASEMENTS ? PLEASE UPDATE
 PLAN. WOULD ALSO NEED UE FOR NEW IRRIGATION WATER
 SERVICE AND METER BOX. ON BOUNDARY & TOPOGRAPHY SURVEY
 (SHEET V-2), THERE IS A LISTED UTILITY EASEMENT ? IF
 THAT STILL EXISTS MAYBE IT CAN BE INCORPORATED ON SHEET
 C-8. IF NOT EXISTING, THEN ALSO WOULD LIKE UTILITY
 EASEMENTS FOR EXISTING WATER SERVICES TO EXISTING
 HOTEL. CIVIL PLAN ALSO SHOWS A WATER MAIN APPROACHING
 THOSE WATER SERVICES FROM ROAD. PLEASE VERIFY IF THAT
 IS DRAWN CORRECTLY AND IF CITY-OWNED. IF SO, THEN NEED
 UE FOR THAT ALSO.
 RESPONSE: COMPLIED; PLEASE REFER TO THE REVISED CIVIL
 PLANS.
 CAN'T FIND WHERE UE UPDATED. ALSO SEE SOME BACKFLOWS
 INSIDE THE UE - NEED REVISION.
 2. PLEASE LABEL FIRELINE POINT OF SERVICE GATE VALVE
 ADJACENT TO WATER MAIN.
 RESPONSE: COMPLIED; PLEASE REFER TO THE REVISED CIVIL
 PLANS.
 CAN'T FIND WHERE LABELING WAS ADDED -> LOOKS TO STILL
 NEED IT.
 3. DEMOLITION PLAN DID NOT HAVE A LABEL WITH WHAT IS
 HAPPENING TO OLD EXISTING IRRIGATION WATER SERVICE AND
 BACKFLOW PREVENTER FOR EXISTING HOTEL. AS-BUILT PLAN
 ALSO SHOWS IT ARRANGED DIFFERENTLY. PLEASE VERIFY
 CONFIGURATION. IS IT GOING TO BE CUT & CAPPED, REMOVED,
 OR LEFT IN PLACE AS-IS? THERE WAS ANOTHER COMMENT
 RELATED TO THIS FROM ENGINEERING.
 RESPONSE: COMPLIED; PLEASE REFER TO THE REVISED CIVIL
 PLANS.
 CAN'T FIND WHERE THIS WAS UPDATED.
 NEW COMMENT:
 -FIRELINE SHOWING LABELS AS 8 IN. AND 6 IN. - IS THAT
 CORRECT OR IS ONE OF THEM A MISTAKE?
  