2020-05-26 10:24:41THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 5/01/2020 SUBMITTAL REVIEW PACKAGE. THEY CAN BE
 ADDRESSED PRIOR TO THE ENGINEERING PERMIT APPLICATION
 SUBMITTAL.
  
 1. SHEET 2 OF 8 EROSION CONTROL
 A. SHOW PROTECTION OF INLETS WITHIN THE ELECTRONICS WAY
 RIGHT-OF-WAY.
 B. SHOW SIDEWALK DEMOLITION FOR THE PROPOSED NORTH AND
 SOUTH DRIVEWAYS.
  
 2. SHEET 3 OF 8 ENGINEERING PLAN
 A. PROVIDE THE PROPOSED ELEVATION TO BE CORED AT THE
 EXISTING DRAINAGE STRUCTURE WEST OF THE CONTROL
 STRUCTURE.
 B. THE MINIMUM PERIMETER ELEVATION IS SHOWN AS 14.30
 FEET NAVD AT THE TWO DRIVEWAYS AND ALONG THE EDGE OF
 PAVEMENT OF THE NORTH STORAGE AREA. THIS ELEVATION IS
 TO BE SET EQUAL TO OR ABOVE THE MINIMUM ELEVATION FOR
 CONTROLLED STORMWATER DISCHARGE FROM THE SITE PER SFWMD
 ERP CRITERIA. THE WEIR ELEVATION AT THE CONTROL
 STRUCTURE IS SET AT 14.30 FEET NAVD, THE SAME AS THE
 PERIMETER ELEVATION. IS A CONTROL STRUCTURE NEEDED?
 C. IT APPEARS THE SITE IS DESIGNED TO FLOOD PRIOR TO
 ANY OFFSITE DISCHARGE. NONE OF THE ONSITE CATCH BASIN
 GRATE ELEVATIONS ARE LOWER THAN THE WEIR ELEVATION.
  
 3. SHEET 4 OF 8 CROSS SECTIONS
 A. ADD VERTICAL DATUM NOTE AND CONVERSION EQUATION TO
 NGVD1929.
 B. LABEL THE LANDSCAPE BUFFERS AND DIMENSIONS ON THE
 APPROPRIATE SECTIONS.
 C. SHOW A BERM AND MINIMUM BERM/PERIMETER ELEVATION ON
 THE APPROPRIATE SECTIONS.
 D. SHOW AND DIMENSION THE LOCATION OF PROPOSED/EXISTING
 FENCES FROM PROPERTY LINE ON THE SECTIONS. [REPEAT
 COMMENT]
 E. SECTION B-B
 1. THE GRAVITY WALL APPEARS TO BE FACING THE WRONG
 DIRECTION.
 2. CONFIRM THE GRAVITY WALL CAN BE LOCATED WITHIN THE
 LANDSCAPE BUFFER.
 F. SECTION D-D
 THE RESPONSE REGARDING THE ENCROACHMENT ONTO THE
 PROPERTY NORTH OF 3200 ELECTRONICS WAY STATED BOTH
 PROPERTIES ARE OWNED BY THE SAME OWNER. THE PROPERTY
 APPRAISER?S WEBSITE INDICATES SEPARATE ENTITIES OWN
 EACH PARCEL. THE CITY?S LAW DEPARTMENT HAS BEEN ASKED
 IF A MORE FORMAL DOCUMENT (AND PERHAPS RECORDED IN THE
 PUBLIC RECORDS) IS NEEDED BEYOND THE LETTER THAT WAS
 PROVIDED BY THE NORTH PROPERTY OWNER.
 G. SECTION E-E ?
 1. ADD THE CROSS SLOPE FOR THE SIDEWALK.
 2. STEEPEN THE DRIVEWAY SLOPE BEHIND THE SIDEWALK TO
 REDUCE THE LENGTH OF DRIVEWAY DRAINING TO THE RIGHT OF
 WAY.
 H. SECTION G-G ?
 1. ADD THE CROSS SLOPE FOR THE SIDEWALK.
 2. STEEPEN THE DRIVEWAY SLOPE BEHIND THE SIDEWALK TO
 REDUCE THE LENGTH OF DRIVEWAY DRAINING TO THE RIGHT OF
 WAY.
 3. THE PLAN VIEW ON SHEET 3 SHOWS THE 14.30 SPOT GRADE
 MORE THAN 18 FEET FROM THE BACK OF SIDEWALK.
 4. SHEET 5 OF 8
 A. CONTROL STRUCTURE DETAIL ? PROVIDE ELEVATIONS OF
 GRATE, INVERTS AND WEIR.
 B. ADD VERTICAL DATUM NOTE AND CONVERSION EQUATION TO
 NGVD1929.
  