2020-02-28 15:46:42THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 FEBRUARY 11, 2020 REVIEW SUBMITTAL PACKAGE.
  
 1. NO GRADING INFORMATION WAS PROVIDED, JUST FLOW
 ARROWS.
  
 2. PROVIDE A CONDITION ASSESSMENT OF THE MANHOLE TO BE
 MODIFIED ON CONNISTON ROAD AND CONFIRM IT IS LARGE
 ENOUGH TO ACCEPT A PIPE CONNECTION FROM THE SOUTH WITH
 THE THREE OTHER EXISTING PIPE CONNECTIONS.
  
 3. CONSIDER CONNECTING THE ONSITE DRAIINAGE SYSTEM TO
 THE EXISTING CATCH BASIN ON S. OLIVE AVE INSTEAD OF TO
 THE MANHOLE ON CONNISTON ROAD. THE S.OLIVE AVE INLET IS
 DOWNSTREAM OF THE CONNISTON RD MANHOLE.
  
 4. SHOW MIILL AND RESURFACE LIMITS FOR TRENCH CUR ON
 CONNISTON ROAD.
  
 5. THE CITY'S VERTICAL DATUM IS NGVD1929. THE CITY HAS
 ALLOWED THE USE OF NAVD1988 PROVIDED THE CONVERSION
 BETWEEN NAVD1988 AND NGVD1929 IS LISTED ON THE PLAN.
 PROVIDE THE COVERSION EQUATION ON THE SURVEY.
  
 6. LIST VERTICAL DATUM ON THE ENGINEERING PLANS AND
 PROVIDE THE CONVERSION EQUATION TO NGVD1929.
  
 7. SHOW/DIMENSION THE PARKING STALL OVERHANG, IF
 APPLICABLE, ON THE CROSS SECTIONS ON THE ENGINEERING
 PLANS.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT