| 2020-01-03 14:51:53 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, |
| | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM |
| | BEACH FIRE RESCUE. |
| | |
| | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE |
| | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. |
| | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS |
| | ARE SUBMITTED FOR PERMIT. |
| | |
| | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE |
| | PROPOSED PROJECT. |
| | |
| | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE |
| | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A |
| | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED |
| | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN |
| | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY |
| | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER |
| | PROTECTION. |
| | |
| | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY |
| | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING |
| | ALL CONSTRUCTION ACTIVITIES. |
| | |
| | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM |
| | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. |
| | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND |
| | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT |
| | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. |
| | |
| | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE |
| | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE |
| | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. |
| | |
| | 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH |
| | THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, |
| | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. |
| | |
| | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE |
| | OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE, |
| | AND WHETHER IT IS MIXED OR SEPARATED OCCUPANCY. |
| | |
| | 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE |
| | LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER |
| | SUPPLY IS EXISTING OR WILL BE PROVIDED. |
| | |
| | 8. FIRE HYDRANT COULD NOT BE IDENTIFIED ON THE |
| | SUBMITTAL. |
| | |
| | ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS |
| | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED |
| | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF |
| | FIRE PREVENTION. |
| | |
| | ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS |
| | DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE |
| | BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND |
| | FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET |
| | OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER |
| | ARRIVING EMERGENCY VEHICLES. |
| | |
| | 9.THERE IS AN INDICATION OF A BASEMENT, PER NFPA 1, |
| | 13.3.2.2 BASEMENTS EXCEEDING 2500 SQ FT IN NEW |
| | BUILDINGS SHALL BE PROTECTED THROUGHOUT BY AN APPROVED |
| | AUTOMATIC FIRE SPRINKLER SYSTEM. |
| | |
| | 9A) AS APPLICABLE TO THE ABOVE, THE LOCATION OF THE |
| | DDCC FIRE LINE LOCATION(S) ARE NOT INDICATED; HOWEVER, |
| | THEY SHALL MEET THE REQUIREMENTS OF NFPA 24 AND SHALL |
| | BE COORDINATED WITH THE OFFICE OF FIRE MARSHAL, THE |
| | CITY'S ENGINEERS OFFICE, THE LANDSCAPE PLANNER, AND THE |
| | CITY'S PLANNING AND ZONING OFFICE. |
| | |
| | AS APPLICABLE TO THE ABOVE, PROVIDE FOR A FIRE |
| | SPRINKLER AND/OR FIRE ALARM PER THE APPLICABLE |
| | OCCUPANCY CODE. FOR ANY LIFE SAFETY ENGINEERED SYSTEM, |
| | I.E FIRE SPRINKLER AND FIRE ALARM, ENSURE THEY COMPLY |
| | WITH THE REQUIREMENTS OF FS 61G AND SUBMITTED WITH THE |
| | MASTER PLAN. |
| | |
| | 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL |
| | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL |
| | DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, |
| | EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A |
| | PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE |
| | SAFETY FEATURES AND EQUIPMENT. |
| | |
| | 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE |
| | SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY |
| | DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS. |
| | |
| | 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT |
| | DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL. |
| | |
| | 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING |
| | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH |
| | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| |