Plan Review Notes
Plan Review Notes For Project Z19120009
Project Number Z19120009
Review Stop ENG - PPRC
Sequence Number 3
Notes
Date Text
2020-07-13 10:58:40PASSED WITH PROVISOS FOR ENGINEERING SUBMITTAL::
  
 REMOVE OBSOLETE STANDARD DETAILS WS-2 AND WS-4.
  
 SHOW VERTICAL CLEARANCE BETWEEN PROPOSED WATER &
 EXISTING SANITARY PIPE.
  
 LABEL POINT OF SERVICE FOR DOMESTIC WATER.
  
 IF PROPOSED WATER SOURCE FOR IRRIGATION IS WELL WARE,
 DETAIL MUST BE PROVIDED INCLUDING PROPOSED LOCATION,
 SCREENING FOR PUMP, ETC. WHICH WOULD NEED ZONING
 APPROVAL.
  
  
  
  
  