Notes
Date Text
2020-04-25 09:36:36PLEASE UPDATE STANDARD DETAILS TO MOST CURRENT
 VERSIONS.
  
 PLEASE PROVIDE ENLARGED DETAIL OF PROPOSED WATER
 METER/BACKFLOW AREA.
  
 PLEASE PROVIDE CLEARANCES AT PROPOSED UTILITY
 CROSSINGS.
  
  
 COMMENTS FROM MARK HURLEY, CUSTOMER SERVICE SUPERVISOR,
 PUBLIC UTILITIES, [email protected] 561-822-2262
  
 -SEWER DEMAND WAS REFERRED TO IN COMMENT RESPONSE BUT
 NOT LISTED ON THE PLAN C-2. PLEASE ADD.
  
 -WILL THERE BE ANY IRRIGATION? IF SO AND RUNS OFF CITY
 WATER, ADD TO DEMAND CALCULATION.
  
 -RELOCATE 6? GATE VALVE NEAREST DCDA A BIT DOWNSTREAM
 SO THAT IT SHUTS OFF ONLY THE FIRELINE AND LABEL AS
 POINT OF SERVICE FOR FIRELINE.
  
 -CANNOT SEE UTILITY EASEMENT BOUNDARIES NEAR THE WATER
 METERS. PLEASE MAKE CLEARER. FIRE AND DOMESTIC BACKFLOW
 ASSEMBLIES CANNOT BE IN UTILITY EASEMENTS.
  
 -WATER SERVICE PIPE MATERIAL NOT LABELED.
  
 -EACH 2? METER SHOULD HAVE IT?S OWN TAP AND SERVICE
 LINE FROM THE 6? PIPE.
  
 -NEED UTILITY EASEMENT FOR CITY FIRE HYDRANT LOCATED
 NEAR SW CORNER OF PROPERTY.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 DIRECT: (561) 494-1098 [email protected]
  