| 2020-01-07 07:29:10 | SHOW ADDRESS ON PLANS |
| | PROVIDE WATER AND SEWER DEMANDS ON PLANS. WILL EXISTING |
| | METERS BE SUFFICIENT? WILL SANITARY NEED TO BE UPSIZED |
| | DOWNSTREAM? |
| | PROVIDE CCTV OF SEWER AND STORM ALONG PROJECT FRONTAGE |
| | CONFIRM/VERIFY SANITARY FLOW DIRECTION |
| | SHOW MATERIALS, PIPE SIZES ETC. |
| | SHOW CONFLICTS AND PROFILES AT PROPOSED UTILITY |
| | CROSSINGS. |
| | SHOW FM IN RAILROAD ROW |
| | FOR ENGINEERING SUBMITTAL, SHOW ENLARGED DETAIL OF |
| | PROPOSED METER LOCATION WITH EASEMENT FOR METER |
| | PLACEMENT. |
| | |
| | FOLLOWING COMMENTS FROM MARK HURLEY, PUBLIC UTILITIES |
| | CUSTOMER SERVICE SUPERVISOR, [email protected], |
| | 561-822-2262: |
| | -THE PLAN LOOKS TO BE TAKING INTO ACCOUNT THE |
| | FORTHCOMING BANYAN STREETSCAPE PROJECT, BUT NEEDS TO BE |
| | PREPARED IF CHANGES OCCUR. FOR INSTANCE, THE EXISTING |
| | WATER SERVICES AND METER BOXES ON BANYAN MAY POSSIBLY |
| | BE ELIMINATED (BOTH OF THEM). IF THE ONE TO THE |
| | SOUTHWEST IS NOT ELIMINATED AND GOING TO USE 2 IN. |
| | METER, WOULD LIKE IT BROUGHT OUT OF SIDEWALK AND INTO |
| | SMALL GRASS U.E. NOT SURE IF PLAN ACCOUNTED FOR |
| | EXISTING SERVICE TO FAR SOUTHEAST. |
| | -THERE MAY BE A FORTHCOMING TAMARIND UTILITY PROJECT |
| | THAT HAS BEEN IN PLANNING FOR LONG TIME. PLAN MAY NEED |
| | ADJUSTMENT IF THAT TAKES PLACE BEFOREHAND. |
| | -DOMESTIC METER SIZE NEEDS TO BE DETERMINED AS METERS |
| | ABOVE 2 IN. REQUIRE MUCH MORE SPACE AND NEED TO BE |
| | ABOVE-GROUND AND OUT OF TRAFFIC. |
| | -WATER MAIN MATERIAL NOT SHOWN ON LABEL. SERVICE SIZE |
| | AND METER SIZE ALSO NOT SHOWN AND LABELED. |
| | -DOMESTIC BACKFLOW ASSEMBLY NOT SHOWN. RECOMMEND |
| | PARALLEL DOMESTIC BACKFLOW ASSEMBLIES SO CUSTOMER IS |
| | NOT WITHOUT WATER DURING MAINTENANCE. THEY CANNOT BE |
| | LOCATED INSIDE BUILDING, IN SIDEWALK, OR IN ROW. |
| | -ADD WS SD # TO LABEL IF CONSTRUCTING SOMETHING THAT |
| | WOULD REFERENCE IT SUCH AS A FIRELINE BACKFLOW |
| | ASSEMBLY. PUT COPY OF THAT WATER SERVICE STANDARD |
| | DETAIL IN PLAN. |
| | -NEED LABEL CONFLICT CROSSING OF FIRELINE WITH FM & S. |
| | PREFER WATER LINES ABOVE SEWER LINES WHEN POSSIBLE. |
| | -SIZE OF WET TAP NOT LABELED ALONG WITH SIZE OF |
| | FIRELINE AND SIZE OF DCDA. TYPE OF MATERIAL IS ALSO NOT |
| | ON LABEL. NEED POINT OF SERVICE VALVE AT PROPERTY LINE |
| | ? LIKE IT TO BE OUT OF HEAVY TRAFFIC WHEN POSSIBLE. |
| | -20 IN. WATER MAIN MATERIAL NOT LABELED. |
| | -THE WESTERN DRIVEWAY IS BEING BUILT OVER LARGE SEWER |
| | PIPES (FM & S) WHICH COULD BE PROBLEMATIC IF |
| | MAINTENANCE WERE NEEDED WHERE DRIVEWAY HAD TO BE SHUT |
| | DOWN AND DRIVEWAY EXCAVATED. CAN GARAGE PARKING STILL |
| | BE FUNCTIONALLY USED IN THAT EVENT? |
| | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR |
| | CONCERNS, THANKS. |
| | RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR WPB, FL 33401 (MAILING |
| | ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098 |
| | FAX: (561) 494-1116 MOBILE: (561) 246-9525 |
| | EMAIL: [email protected] WWW.WPB.ORG/ENGINEERING |
| | |
| |