Plan Review Notes
Plan Review Notes For Project Z19110020
Project Number Z19110020
Review Stop ENG - PPRC
Sequence Number 5
Notes
Date Text
2021-03-26 11:55:05ADDITIONAL PROVISO:
 -IRRIGATION PLAN AND DETAILS CALL OUT PVB BACKFLOW
 ASSEMBLY ADJACENT WATER METER. THAT DOES NOT MATCH
 UTILITY PLAN AND NEEDS TO BE RP TYPE INSTEAD.
 INSTALLATION OF BACKFLOW ASSEMBLY AND PIPING AROUND IT
 MUST COMPLY WITH PUBLIC UTILITIES WATER SERVICE
 STANDARD DETAIL FOR SMALL BACKFLOW ASSEMBLIES (WS-6)
 AND BE LEAD-FREE COMPLIANT AND USC-APPROVED.
  
 COMMENTS PER MARK HURLEY
 FIELD CUSTOMER SERVICE SUPERVISOR
 CITY OF WEST PALM BEACH PUBLIC UTILITIES
 561-822-2262
  