Plan Review Notes
Plan Review Notes For Project Z19110020
Project Number Z19110020
Review Stop ENG - PPRC
Sequence Number 4
Notes
Date Text
2021-01-06 08:38:47PASSED WITH PROVISOS:
  
 COMMENTS PER MARK HURLEY, FIELD CUSTOMER SVC.
 SUPERVISOR, CITY OF WPB PUB. UTIL., [email protected],
 561-822-2262:
 -FOR FORMAL ENGINEERING SUBMITTAL:
 1) ADD GATE VALVES AT THE INTERSECTIONS FOR THE
 REPLACEMENT 8INCH DIP WATER MAIN ON 2ND ST.
 2) VERIFY EXISTING WATER MAIN ADJACENT EAST SIDE OF
 PROPERTY ? (IT IS NOT SHOWING UP ON OUR GIS)
 3) LABEL WATER MAINS ON ROSEMARY AVE WITH PIPE MATERIAL
 TYPE AND SIZE.
 -THE INCLUDED WATER SERVICE STANDARD DETAILS STILL HAVE
 SOME WITH OUTDATED REVISION, WRONG TYPE USED, AND SOME
 ARE MISSING SUCH SMALL WATER SERVICE AND SMALL BACKFLOW
 ASSEMBLY. PLEASE ADD AND REVISE THEM AT FORMAL
 ENGINEERING SUBMITTAL.
 -IN ADDITION TO THE BACKFLOW COVENANT RECORDING
 REQUIREMENT, FIRELINE BACKFLOW ASSEMBLY USED INSIDE
 BUILDING MUST BE USC APPROVED FOR THE PROPOSED
 ORIENTATION.
 -CONFIRM THAT THE FDC IS AN ACCEPTABLE DISTANCE FROM
 THE NEAREST FIRE HYDRANT.
 -LANDSCAPE PLAN LP-1 SHOWS A TREE CLOSE TO GATE VALVES
 NEAR TAP FOR THE DOMESTIC & IRRIGATION WATER SERVICES.
 PLEASE PROVIDE MORE CLEARANCE AND/OR ADD ROOT BARRIERS.
 -WILL PROVIDE FURTHER DETAILED COMMENTS FOR MINOR
 ISSUES AT FORMAL ENGINEERING SUBMITTAL.
  