| 2020-12-03 14:03:00 | COMMENTS PER RICK ROSSANO, PROJ. COORD, CITY OF WPB |
| | ENG. SVCS., [email protected], 561-494-1098: |
| | |
| | SUBMITTED LOS ANALYSIS SUMMARY TABLE AVG. DAILY FLOWS |
| | DO NOT MATCH THOSE ON SHEET C2.1 OF CIVIL PLANS. |
| | |
| | FOR ENGINEERING SUBMITTAL, PROVIDE PROFILES OF ALL |
| | PROPOSED UTILITY CROSSINGS. |
| | |
| | FOR ENGINEERING SUBMITTAL, PROVIDE ENLARGED DETAIL ON |
| | PLANS OF PROPOSED LOCATION OF WATER METERS AND BACKFLOW |
| | PREVENTION UNITS. |
| | |
| | FOR ENGINEERING SUBMITTAL, PLEASE LABEL MATERIALS OF |
| | ALL EXISTING CITY WATER & SEWER INFRASTRUCTURE IN ROW. |
| | |
| | FOR ENGINEERING SUBMITTAL, PLEASE PROVIDE PROJECT |
| | ADDRESS. |
| | |
| | COMMENTS PER MARK HURLEY, FIELD CUSTOMER SVC. |
| | SUPERVISOR, CITY OF WPB PUB. UTIL., [email protected], |
| | 561-822-2262: |
| | -SOME PRIOR COMMENTS WERE NOT SATISFIED. WILL LIST ONES |
| | NEEDING ATTENTION AGAIN: |
| | -CIVIL PLAN WATER SERVICE STANDARD DETAILS ARE OLD |
| | REVISION. PLEASE REPLACE WITH MOST UPDATED REVISION. |
| | -4 IN. DOMESTIC METER NEEDS TO BE ABOVE-GROUND |
| | INSTALLATION AND NOT UNDERGROUND VAULT INSTALLATION. |
| | PLEASE ADD ABOVE-GROUND WORDING TO LABEL ON C1.2 AND |
| | REPLACE THE VAULT STANDARD DETAIL ON C2.3 WITH THE |
| | ABOVE-GROUND INSTALLATION. |
| | -4 IN. DIP WATER SERVICE IS BRANCHED INTO 1.5 IN. AND 4 |
| | IN. METERS. PLAN DESIGNER NEED VERIFY CUSTOMER WITH NOT |
| | HAVE PROBLEMS USING WATER WITH THAT SETUP. |
| | ADDITIONAL COMMENTS: |
| | -NO WATER MAIN VALVES IN THE STREETS ARE SHOWN. PLEASE |
| | ADD ALL EXISTING AND PROPOSED GATE VALVES TO WATER |
| | PLAN. |
| | -ON WATER PLAN, REMOVE WORDING RPZ IN PUMP ROOM SINCE |
| | CONTAINMENT DOMESTIC BACKFLOW ASSEMBLY WILL BE OUTSIDE |
| | ADJACENT THE METER. |
| | -WATER MAIN ON SAPODILLA IS NOT LABELED WITH PIPE |
| | SIZING OR MATERIAL TYPE. PLEASE ADD SO CAN VERIFY WILL |
| | ACCOMMODATE NEW 8IN. DIP. SIMILARLY ADD PIPE MATERIAL |
| | TYPE TO WATER MAIN LABELING ON ROSEMARY. |
| | -FIRE HYDRANT AT ROSEMARY AND 2ND IS PROPOSED TO BE IN |
| | THE MIDDLE OF PEDESTRIAN SIDEWALK TRAFFIC. PLEASE |
| | RELOCATE FIRE HYDRANT TO NEARBY AREA OUT OF PEDESTRIAN |
| | TRAFFIC SINCE WATER MAIN IS BEING REPLACED. |
| | -FDC IS PRIVATELY OWNED AND SHOULD NOT BE IN ROW. |
| | PLEASE RELOCATE AND MAKE SURE NEW LOCATION IS NOT IN |
| | PEDESTRIAN TRAFFIC. |
| | -THERE IS A CIRCULAR OBJECT IN SIDEWALK SLIGHTLY NE OF |
| | FDC. PLEASE DESCRIBE WHAT IT IS AND LABEL ON PLAN. |
| | -NEAR THE ENTRANCE ON 2ND ST, THERE APPEARS TO BE SOME |
| | FIND OF GATES ENCROACHING INTO SIDEWALK. VERIFY IF THAT |
| | IS ALLOWED BY CITY WPB. |
| | -DCDA MAY NOT BE IN UNDERGROUND VAULT. NEED UPDATE |
| | WATER PLAN. |
| | -PAVEMENT RESTORATION LIMITS NEED TO BE UPDATED TO |
| | REFLECT THE ENTIRE WATER MAIN THAT IS BEING REPLACED ON |
| | 2ND ST. ALSO INCLUDE THE INTERSECTIONS. |
| | -EXISTING FIRE HYDRANT AT SAPODILLA AND 2ND STILL |
| | APPEARS TO BE MISSING FROM WATER PLAN. PLEASE ADD AND |
| | LABEL. |
| | -CANNOT LOCATE A DEMO PLAN. PLEASE SUBMIT DEMO PLAN IF |
| | THERE WILL BE DEMOLITION. |
| | -STILL CANNOT LOCATE ON WATER PLAN EXISTING SMALL WATER |
| | SERVICES ON 2ND AND 3RD ST. PLEASE ADD TO PLAN |
| | -THERE ARE SEVERAL WATER METER BOXES IN THE SIDEWALK ON |
| | SOUTH SIDE OF 3RD ST. PLEASE SHOW THEM ON THE PLANS AND |
| | LABEL WHAT IS HAPPENING TO THEM. |
| | -WILL ALL OF THE PROPOSED BUILDINGS FOR THE PROJECT BE |
| | FED BY THE WATER SERVICES ON 2ND ST? |
| | -LANDSCAPE TREES ON 2ND ST ARE CONFLICTING WITH THE |
| | PROPOSED WATER MAIN. THE WORST ONE IS NEAR THE EAST |
| | INTERSECTION ISLAND WHERE TREE AND WATER MAIN ARE AT |
| | SAME LOCATION. THE OTHER TREES ARE CLOSE TO THE WATER |
| | MAIN IN THE ISLANDS. PLEASE RESOLVE THOSE CONFLICTS. |
| | |
| |