| 2020-11-02 22:58:48 | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE |
| | 10/2/2020 SUBMITTAL REVIEW PACKAGE: |
| | |
| | 1. SHOW THE PROPERTY LINES/RIGHT OF WAY LINES. |
| | |
| | 2. SHOW THE EXISTING IMPROVEMENTS TO THE OPPOSITE RIGHT |
| | OF WAY LINES. |
| | |
| | 3. PROVIDE CROSS SECTIONS FROM ROAD CENTERLINE TO FACE |
| | OF BUILDING. LABEL STREET RIGHT OF WAY LINE, AND |
| | HORIZONTAL DIMENSIONS FOR TRAVEL LANE, EDGE OF |
| | PAVEMENT, RIGHT OF WAY, SIDEWALK WIDTH, LANDSCAPE WIDTH |
| | AND BUILDING SETBACK FROM PROPERTY LINE. |
| | |
| | 4. PROVIDE CROSS SECTIONS FOR WEST PROPERTY LINE (NORTH |
| | AND SOUTH OF ALLEY) SHOWING PERIMETER BERM (IF |
| | REQUIRED) OR SWALE TO PREVENT DIRECT RUNOFF TO ADJACENT |
| | PROPERTY, AND BUILDING OFFSET DIMENSION. |
| | |
| | 5. BULBOUTS ALONG 2ND STREET APPEAR TO TRAP WATER ALONG |
| | THE CURB AND GUTTER. |
| | |
| | 6. CONSIDER CONNECTING S-203 TO EXISTING CURB INLET TO |
| | THE NORTHWEST OF STRUCTURE INSTEAD OF S-204. |
| | |
| | 7. ENGINEERING PERMIT SUBMITTAL TO INCLUDE CHANGE IN |
| | HGL FOR 3RD STREET AND ROSEMARY AVE. DRAINAGE SYSTEMS. |
| | |
| | 8. PROVIDE CONVERSION EQUATION BETWEEN NAVD1988 AND |
| | NGVD1929 ON ALL SHEETS WITH ELEVATION INFORMATION. |
| | |
| | 9. PROVIDE CONVERSION EQUATION BETWEEN NAVD1988 AND |
| | CITY DATUM OF NGVD1929 ON THE SURVEY. |
| | |
| | 10. SABAL PALMS PROPOSED OVER PROPOSED STORM PIPE ALONG |
| | WEST PROPERTY LINE. |
| | |
| | TRACY WARD, P.E. |
| | SENIOR STORMWATER ENGINEER |