| 2020-10-16 19:49:03 | COMMENTS PER RICK ROSSANO, PROJ. COORD, CITY OF WPB |
| | ENG. SVCS., [email protected], 561-494-1098: |
| | |
| | PROVIDE CALCULATIONS ON PLANS OF EXISTING AND PROPOSED |
| | DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM AND PEAK) |
| | AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE PER FAC |
| | 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER. |
| | |
| | PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE |
| | DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB |
| | DEVELOPMENT APPLICATION). |
| | |
| | FOR ENGINEERING SUBMITTAL, SHOW VERTICAL DATUM AND |
| | DATUM CONVERSION INFORMATION (NAVD 88 AND NGVD 29). |
| | |
| | FOR ENGINEERING SUBMITTAL, SHOW ALL FRANCHISE |
| | UTILITIES. |
| | |
| | FOR ENGINEERING SUBMITTAL, ADD PAVEMENT RESTORATION |
| | NOTE. |
| | |
| | FOR ENGINEERING SUBMITTAL, PROVIDE ENLARGED DETAIL ON |
| | PLANS OF PROPOSED LOCATION OF WATER METER AND BACKFLOW |
| | PREVENTION. PROVIDE UTILITY EASEMENTS TO ALLOW ACCESS |
| | FOR CITY PERSONNEL TO PROPOSED UTILITIES INCLUDING |
| | WATER METERS. |
| | |
| | COMMENTS PER MARK HURLEY, FIELD CUSTOMER SVC. |
| | SUPERVISOR, CITY OF WPB PUB. UTIL., [email protected], |
| | 561-822-2262: |
| | |
| | -CIVIL PLAN WATER SERVICE STANDARD DETAILS ARE OLD |
| | REVISION. PLEASE REPLACE WITH MOST UPDATED REVISION. |
| | SHEET C1.2 |
| | -THERE APPEAR TO BE SEVERAL WATER MAIN GATE VALVES IN |
| | CURBS. PLEASE DO NOT LOCATE VALVE BOXES IN CURBS. |
| | -4 IN. DOMESTIC METER NEEDS TO BE ABOVE-GROUND |
| | INSTALLATION AND NOT UNDERGROUND VAULT INSTALLATION. |
| | PLEASE ADD ?ABOVE-GROUND? TO LABEL AND REPLACE THE WS-6 |
| | WITH THE CORRECT STANDARD DETAILS. |
| | -RECOMMEND PARALLEL/DUAL BACKFLOW ASSEMBLIES FOR THE 4 |
| | IN. DOMESTIC WATER SERVICE TO MINIMIZE WATER OUTAGES |
| | DURING BACKFLOW MAINTENANCE. |
| | -4 IN. DIP WATER SERVICE IS BRANCHED INTO 1.5 IN. AND 4 |
| | IN. METERS. PLAN DESIGNER NEED VERIFY CUSTOMER WITH NOT |
| | HAVE PROBLEMS USING WATER WITH THAT SETUP. FOR |
| | ENGINEERING SUBMITTAL, ALSO LABEL THAT BRANCH WITH TYPE |
| | OF FITTING/TAP AND WATER SERVICE PIPING FEEDING 1.5 IN. |
| | IRRIGATION METER. |
| | -FOR FORMAL ENGINEERING SUBMITTAL ADD WATER DEMAND |
| | CALCULATIONS TO WATER PLAN AND LABEL FIRELINE POINT OF |
| | SERVICE GATE VALVE. |
| | -UTILITY EASEMENTS ARE NEEDED AROUND WATER METERS AND |
| | WATER SERVICE PIPING ON PRIVATE PROPERTY. PLEASE ADD |
| | AND LABEL ON PLAN. |
| | -EXISTING FIRE HYDRANTS STILL APPEAR TO BE MISSING FROM |
| | PLAN. PLEASE ADD AND LABEL. |
| | -4 IN. DOMESTIC WATER SERVICE HAS AN ISOLATION BACKFLOW |
| | ASSEMBLY CALLED OUT IN FIRE ROOM. THIS MIGHT BE AN |
| | ERROR BETWEEN REVISIONS. CONTAINMENT BACKFLOW ASSEMBLY |
| | FOR DOMESTIC MAY NOT BE INSIDE BUILDING. |
| | -8 IN. DCDA MAY NOT BE UNDERGROUND. IF NEED TO MEET |
| | FIRE DEPARTMENT REQUIREMENTS REGARDING COLLAPSE ZONES, |
| | DCDA MAY BE LOCATED INSIDE BUILDING IF BACKFLOW |
| | COVENANT IS COMPLETED AND SUBMITTED BY PROPERTY OWNER. |
| | -SHOW EXISTING WATER SERVICES RUNNING NORTH AND SOUTH |
| | OF EXISTING WATER MAINS ON 2ND ST FOR FORMAL |
| | ENGINEERING SUBMITTAL. |
| | -VERIFY THAT WATER MAIN TAPS AND PAVEMENT RESTORATION |
| | ARE IN COMPLIANCE WITH STANDARD DETAIL P-4. IF P-4 IS |
| | GOING TO BE USED, ADD TO PLAN. |
| | -CANNOT FIND NUMERICAL PROPERTY ADDRESS ON PLAN. PLEASE |
| | ADD BEFORE FINAL COPY. |
| | |
| |