Plan Review Notes
Plan Review Notes For Project Z19110020
Project Number Z19110020
Review Stop ENG - PPRC
Sequence Number 2
Notes
Date Text
2020-10-16 19:49:03COMMENTS PER RICK ROSSANO, PROJ. COORD, CITY OF WPB
 ENG. SVCS., [email protected], 561-494-1098:
  
 PROVIDE CALCULATIONS ON PLANS OF EXISTING AND PROPOSED
 DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM AND PEAK)
 AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE PER FAC
 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER.
  
 PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE
 DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB
 DEVELOPMENT APPLICATION).
  
 FOR ENGINEERING SUBMITTAL, SHOW VERTICAL DATUM AND
 DATUM CONVERSION INFORMATION (NAVD 88 AND NGVD 29).
  
 FOR ENGINEERING SUBMITTAL, SHOW ALL FRANCHISE
 UTILITIES.
  
 FOR ENGINEERING SUBMITTAL, ADD PAVEMENT RESTORATION
 NOTE.
  
 FOR ENGINEERING SUBMITTAL, PROVIDE ENLARGED DETAIL ON
 PLANS OF PROPOSED LOCATION OF WATER METER AND BACKFLOW
 PREVENTION. PROVIDE UTILITY EASEMENTS TO ALLOW ACCESS
 FOR CITY PERSONNEL TO PROPOSED UTILITIES INCLUDING
 WATER METERS.
  
 COMMENTS PER MARK HURLEY, FIELD CUSTOMER SVC.
 SUPERVISOR, CITY OF WPB PUB. UTIL., [email protected],
 561-822-2262:
  
 -CIVIL PLAN WATER SERVICE STANDARD DETAILS ARE OLD
 REVISION. PLEASE REPLACE WITH MOST UPDATED REVISION.
 SHEET C1.2
 -THERE APPEAR TO BE SEVERAL WATER MAIN GATE VALVES IN
 CURBS. PLEASE DO NOT LOCATE VALVE BOXES IN CURBS.
 -4 IN. DOMESTIC METER NEEDS TO BE ABOVE-GROUND
 INSTALLATION AND NOT UNDERGROUND VAULT INSTALLATION.
 PLEASE ADD ?ABOVE-GROUND? TO LABEL AND REPLACE THE WS-6
 WITH THE CORRECT STANDARD DETAILS.
 -RECOMMEND PARALLEL/DUAL BACKFLOW ASSEMBLIES FOR THE 4
 IN. DOMESTIC WATER SERVICE TO MINIMIZE WATER OUTAGES
 DURING BACKFLOW MAINTENANCE.
 -4 IN. DIP WATER SERVICE IS BRANCHED INTO 1.5 IN. AND 4
 IN. METERS. PLAN DESIGNER NEED VERIFY CUSTOMER WITH NOT
 HAVE PROBLEMS USING WATER WITH THAT SETUP. FOR
 ENGINEERING SUBMITTAL, ALSO LABEL THAT BRANCH WITH TYPE
 OF FITTING/TAP AND WATER SERVICE PIPING FEEDING 1.5 IN.
 IRRIGATION METER.
 -FOR FORMAL ENGINEERING SUBMITTAL ADD WATER DEMAND
 CALCULATIONS TO WATER PLAN AND LABEL FIRELINE POINT OF
 SERVICE GATE VALVE.
 -UTILITY EASEMENTS ARE NEEDED AROUND WATER METERS AND
 WATER SERVICE PIPING ON PRIVATE PROPERTY. PLEASE ADD
 AND LABEL ON PLAN.
 -EXISTING FIRE HYDRANTS STILL APPEAR TO BE MISSING FROM
 PLAN. PLEASE ADD AND LABEL.
 -4 IN. DOMESTIC WATER SERVICE HAS AN ISOLATION BACKFLOW
 ASSEMBLY CALLED OUT IN FIRE ROOM. THIS MIGHT BE AN
 ERROR BETWEEN REVISIONS. CONTAINMENT BACKFLOW ASSEMBLY
 FOR DOMESTIC MAY NOT BE INSIDE BUILDING.
 -8 IN. DCDA MAY NOT BE UNDERGROUND. IF NEED TO MEET
 FIRE DEPARTMENT REQUIREMENTS REGARDING COLLAPSE ZONES,
 DCDA MAY BE LOCATED INSIDE BUILDING IF BACKFLOW
 COVENANT IS COMPLETED AND SUBMITTED BY PROPERTY OWNER.
 -SHOW EXISTING WATER SERVICES RUNNING NORTH AND SOUTH
 OF EXISTING WATER MAINS ON 2ND ST FOR FORMAL
 ENGINEERING SUBMITTAL.
 -VERIFY THAT WATER MAIN TAPS AND PAVEMENT RESTORATION
 ARE IN COMPLIANCE WITH STANDARD DETAIL P-4. IF P-4 IS
 GOING TO BE USED, ADD TO PLAN.
 -CANNOT FIND NUMERICAL PROPERTY ADDRESS ON PLAN. PLEASE
 ADD BEFORE FINAL COPY.
  