2019-12-05 12:18:33PROVIDE CALCULATIONS ON PLANS OF EXISTING AND PROPOSED
 DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM AND PEAK)
 AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE PER FAC
 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER.
  
 PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND STORM
 DRAINAGE LINES ALONG ENTIRE PROJECT FRONTAGE.
  
 PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY OF
 WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC RIGHT
 OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF YOUR
 PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1079 FOR FURTHER
 ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION
 ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD
 SURVEY, POT-HOLING, SOFT DIGS ETC.
  
 AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS OF
 ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES,
 INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND
 SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES,
 METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE
 SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING
 GRADES, PIPES SIZES, MATERIALS, ELEVATIONS,
 ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL
 INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER
 LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN
 VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
 ADDITIONALLY, PLAN VIEW SHALL SHOW ALL EXISTING AND
 PROPOSED UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER
 OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED ON THE
 RIGHT-OF-WAY.
  
 PLEASE CLEARLY SHOW CITY RIGHTS OF WAY.
  
 PROVIDE PROFILE AND CLEARANCES AT ALL UTILITY
 CROSSINGS.
  
 SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION
 (NAVD 88 AND NGVD 29).
  
 CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 RIGHT OF WAY.
  
 PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE
 DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB
 DEVELOPMENT APPLICATION).
  
 PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
  
 PROVIDE UTILITY EASEMENTS TO ALLOW ACCESS FOR CITY
 PERSONNEL TO PROPOSED UTILITIES INCLUDING WATER METERS.
  
 PLEASE PROVIDE CCTV OF UPSTREAM SANITARY LINES TO
 NORTH, SOUTH AND WEST.
  
 MANHOLE ON ROSEMARY AVE. WILL REQUIRE REHAB.
  
 PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR
 PROPOSED SANITARY LATERALS.
  
 PROVIDE ENLARGED DETAIL ON PLANS OF PROPOSED LOCATION
 OF WATER METER AND BACKFLOW PREVENTION.
  
 FOR FORMAL ENGINEERING SUBMITTAL, SHOW ALL ADJACENT
 ADDRESSES AND SANITARY LATERALS TO BE AFFECTED BY NEW
 SERVICE BEING INSTALLED ALONG 2ND ST.
  
 THE FOLLOWING COMMENTS ARE PER MARK HURLEY, PUBLIC
 UTILITIES CUSTOMER SERVICE SUPERVISOR, 561-822-2262
 [email protected]
  
 -EXISTING WATER SERVICES NOT SHOWN ? SHOULD BE SHOWN
 AND LABELED ON PLAN ALONG WITH WHAT HAPPENING TO THEM.
  
 -NEW WATER SERVICES ON 2ND ST ARE CROSSING OTHER
 UTILITIES. EACH CROSSING SHOULD BE LABELED WITH HOW
 CONFLICT IS RESOLVED.
  
 -DOMESTIC METER SHOULD BE INSTALLED ABOVE-GROUND AND
 LABELED AS SUCH ON PLAN. WOULD NEED U.E. AROUND IT.
 LOCATION AREA LOOKS THIN -> NOT SURE IF WOULD HAVE
 ENOUGH ROOM FOR IT -> NO PART OF IT INCLUDING BYPASS
 BOXES/LIDS SHOULD BE IN A SIDEWALK. ASSOCIATED BACKFLOW
 ASSEMBLY CANNOT BE INSTALLED ACROSS DRIVEWAY AND INSIDE
 BUILDING -> NEEDS TO BE IMMEDIATELY
 ADJACENT AFTER THE METERED WATER SERVICE ON PRIVATE
 PROPERTY AND NOT IN ANY ROW OR UE. CUSTOMER SHOULD
 CONSIDER PARALLEL BACKFLOW ASSEMBLIES TO MINIMIZE WATER
 OUTAGES DURING BACKFLOW MAINTENANCE.
  
 -DRIVEWAY ENTRANCE LOOKS LIKE WILL CAUSE ACCIDENTS OR
 TRAFFIC CONFUSION. IT?S ONE WAY STREET GOING EAST, BUT
 DRIVERS TURNING INTO DRIVEWAY MUST CROSS OUTGOING
 DRIVERS IN CONFLICT. COULD SOMETHING BE DONE TO
 MINIMIZE THAT CONFLICT?
  
 -FIRE DCDA SHOULD NOT BE LOCATED IN BUILDING UNLESS
 FIRE DEPT. REQUIRES IT INSIDE BUILDING. IF REQUIRED TO
 BE INSIDE BUILDING, PROPERTY OWNER WOULD HAVE TO SUBMIT
 BACKFLOW COVENANT.
  
 -PROPOSED SS ON 2ND ST. LOOKS LIKE CLOSER THAN 10? FROM
 EXISTING WATER MAIN -> UNDERSTAND THIS SHOULD BE AT
 LEAST 10? DISTANCE. CROSSINGS WITH EXISTING WATER MAINS
 AND WATER SERVICES ARE NOT SHOWN AND LABELED WITH HOW
 RESOLVED.
  
 -EXISTING WATER SERVICES FEEDING SOUTH SIDE OF 2ND ST
 FROM THE 6? WATER MAIN ARE NOT SHOWN AND LABELED. SHOW
 ALL OTHERS IN PROJECT AREA AS WELL.
  
 -PLEASE SHOW AND LABEL EXISTING FIRE HYDRANTS.
  
 -E-W ALLEY LOOKS LIKE CITY ROW -> NOT SURE IF CUSTOMER
 GOT APPROVAL TO ELIMINATE ALLEY.
  
 -SAW HISTORIC PICTURE OF LARGE TREE IN VICINITY OF NEW
 WATER SERVICES. IF TREE STILL THERE, TREE SHOULD BE
 RELOCATED OR WATER SERVICES POSITIONED FAR AWAY FROM
 IT.
  
 -OUR GIS SHOWS 30? EXISTING WATER MAIN REDUCING DOWN TO
 24? NEAR SAPODILLA. IF THAT IS CORRECT SHOULD BE SHOWN
 ON PLAN.
  
 -PLAN IS MISSING THE WATER DEMAND CALCULATIONS CHART.
  
 -PLAN SHOULD HAVE SEPARATE ENLARGED PLAN SECTIONS JUST
 FOR THE NEW LARGE METERED WATER SERVICES SHOWING DETAIL
 OF HOW CONSTRUCTED.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO, PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401 (MAILING ADDRESS: P.O. BOX
 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098 FAX:
 (561) 494-1116 MOBILE: (561) 246-9525
 EMAIL: [email protected] WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ, SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401 (MAILING ADDRESS: P.O. BOX
 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1085
 FAX: (561) 494-1116 MOBILE: (561) 644-7301 EMAIL:
 [email protected] WWW.WPB.ORG/ENGINEERING
  
  