| Plan Review Notes For Project Z19110010 |
| Project Number |
Z19110010 |
|
| Review Stop |
ENG - PPRC |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2020-08-27 09:35:12 | PLEASE PROVIDE CCTV AS PREVIOUSLY REQUESTED. | | | | | | FOLLOWING COMMENTS FROM MARK HURLEY, PUBLIC UTILITIES, | | | [email protected], 561-822-2262 | | | | | | FOLLOWUP COMMENTS: | | | | | | 4. CUSTOMER SHOULD CONSIDER INSTALLING PARALLEL | | | DOMESTIC BACKFLOW ASSEMBLIES ON THE DOMESTIC LINE TO | | | MINIMIZE WATER OUTAGE DURING BACKFLOW MAINTENANCE. | | | | | | RESPONSE: PLEASE VERIFY IF THIS IS A REQUIREMENT. DUE | | | TO ROOM CONSTRAINTS IT WOULD BE DIFFICULT TO HAVE | | | MULTIPLE BACKFLOWS. | | | | | | -PARALLEL/DUAL INSTALLATION IS NOT A REQUIREMENT ? ONLY | | | A RECOMMENDATION BY THE UTILITY. CUSTOMER MAY UTILIZE | | | SINGULAR BACKFLOW ASSEMBLY. | | | | | | NEW COMMENTS: | | | | | | -DURING FORMAL ENGINEERING SUBMITTAL, CLARIFY ON WATER | | | PLAN IF 10?U.E. AT SOUTH SIDE OF PROPERTY CURVES AND | | | CONTINUE NORTH ON THE EAST SIDE OF PROPERTY. IF SO, | | | PLEASE ADD LABEL ON EAST SIDE. | | | | | | |
| |