Plan Review Notes
Plan Review Notes For Project Z19110010
Project Number Z19110010
Review Stop ENG - PPRC
Sequence Number 1
Notes
Date Text
2019-12-05 12:12:14PROVIDE CALCULATIONS ON PLANS OF EXISTING AND PROPOSED
 DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM AND PEAK)
 AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE PER FAC
 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER.
  
 PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND STORM
 DRAINAGE LINES ALONG ENTIRE PROJECT FRONTAGE.
  
 PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY OF
 WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC RIGHT
 OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF YOUR
 PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1079 FOR FURTHER
 ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION
 ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD
 SURVEY, POT-HOLING, SOFT DIGS ETC.
  
 AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS OF
 ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES,
 INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND
 SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES,
 METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE
 SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING
 GRADES, PIPES SIZES, MATERIALS, ELEVATIONS,
 ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL
 INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER
 LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN
 VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
 ADDITIONALLY, PLAN VIEW SHALL SHOW ALL EXISTING AND
 PROPOSED UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER
 OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED ON THE
 RIGHT-OF-WAY.
  
 PLEASE LABEL CENTREPARK DR. E.
  
 CITY GIS SHOWS CONTINUOUS 12 IN. DIP WATER MAIN ALONG
 CENTREPARK DR. E. PLANS SHOW EXISTING 8 IN. STUB OUT,
 BUT OUR FILES DO NOT REFLECT AN 8 IN. STUB OUT. PLEASE
 CLARIFY PROPOSED WATER CONNECTION.
  
 PROPOSED CURB WILL ENCROACH ON EXISTING SANITARY
 MANHOLE. AS SUCH, POINT OF SERVICE WILL BE EXISTING
 MANHOLE IN CENTREPARK DR. CONSIDER RUNNING PROPOSED
 SANITARY SERVICE TO EXISTING MANHOLE INSTEAD OF
 PROPOSED NEW MANHOLE.
  
 PLEASE CLEARLY SHOW CITY RIGHTS OF WAY.
  
 PROVIDE PROFILE AND CLEARANCES AT ALL UTILITY
 CROSSINGS.
  
 SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION
 (NAVD 88 AND NGVD 29).
  
 CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 RIGHT OF WAY.
  
 PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE
 DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB
 DEVELOPMENT APPLICATION).
  
 PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
  
 ADJUST PROPOSED METER PLACEMENT TO BE WITHIN EASEMENT;
 BACKFLOWS TO BE ON PRIVATE PROPERTY OUTSIDE OF
 EASEMENT.
  
 PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR
 PROPOSED SANITARY LATERALS.
  
 PROVIDE ENLARGED DETAIL ON PLANS OF PROPOSED LOCATION
 OF WATER METER AND BACKFLOW PREVENTION.
  
 PLEASE LABEL ALL POINTS OF SERVICE.
  
 THE FOLLOWING COMMENTS ARE PER MARK HURLEY, PUBLIC
 UTILITIES CUSTOMER SERVICE SUPERVISOR, 561-822-2262 OR
 [email protected]
  
 -LOOKS LIKE WATER SERVICE PIPING LOCATED ON AND RUNNING
 THROUGH OTHER PRIVATE PROPERTY. COULD BE LEGALLY
 PROBLEMATIC IF OTHER PROPERTY OWNER DOES NOT WANT IT
 THERE. RECOMMEND NOT DOING THAT.
  
 -LOOKS LIKE CUSTOMER PROPOSED PAVER BRICK COMING INTO
 ROW -> NOT SURE IF CUSTOMER ALLOWED TO BUILD INTO ROW.
  
 -LOOKS LIKE CUSTOMER PROPOSED PAVER BRICK BEING BUILT
 WITHIN EXISTING 10? UE ALONG EDGES OF PROPERTY. WOULD
 CREATE USABILITY CONFLICT WITH UE. SOLUTION COULD BE TO
 RELOCATE BRICKWORK BACK AND KEEP AREA GRASSED.
  
 -CUSTOMER SHOULD CONSIDER INSTALLING PARALLEL DOMESTIC
 BACKFLOW ASSEMBLIES ON THE DOMESTIC LINE TO MINIMIZE
 WATER OUTAGE DURING BACKFLOW MAINTENANCE.
  
 -THERE ARE SOME EXISTING TREES IN AREA. TREES SHOULD
 NOT BE LOCATED WITHIN 5? OF WATER SERVICE PIPING.
  
 -IF DOMESTIC METER IS 3? OR GREATER, SHOULD BE
 INSTALLED ABOVE-GROUND.
  
 -ALL OF WATER METER NEEDS TO BE IN ROW OR UE.
  
 -EXISTING WATER UTILITIES NOT SHOWN CLEARLY. SHOULD
 HAVE SEPARATE UTILITY PLAN SHEET HIGHLIGHTING EXISTING
 UTILITIES, AND AN ENLARGED/ZOOMED-IN AREA PLAN OF THE
 WATER SERVICES IN DETAIL.
  
 -CANNOT FIGURE OUT WHERE THE RETAIL IS LOCATED ->
 SHOULD LABEL ON PLAN.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO, PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401 (MAILING ADDRESS: P.O. BOX
 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098 FAX:
 (561) 494-1116 MOBILE: (561) 246-9525
 EMAIL: [email protected] WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ, SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401 (MAILING ADDRESS: P.O. BOX
 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1085
 FAX: (561) 494-1116 MOBILE: (561) 644-7301 EMAIL:
 [email protected] WWW.WPB.ORG/ENGINEERING
  
  