2021-03-26 11:35:30THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 3/2/2021 SUBMITTAL REVIEW SET.
  
 1. THERE APPEAR TO BE A MIXTURE OF NAVD1988 AND
 NGVD1929 ELEVATIONS ON THE PLANS. ALL ELEVATION
 INFORMATION (FFE, SPOT GRADES, INVERT/RIM ELEVATIONS,
 ETC.) SHOULD REFERENCE THE SAME VERTICAL DATUM.
  
 2. LIST THE VERTICAL DATUM REFERENCE ON ALL SHEETS
 (INCLUDING DETAIL SHEETS) WITH ELEVATION INFORMATION
 AND PROVIDE THE CONVERSION TO NGVD1929.
  
 3. CAN MH#3 BE MOVED FURTHER EAST? IT'S NOT CLEAR WHERE
 THE CORNER OF THE BUILDING IS AT THE EAST SIDE OF THE
 EAST DRIVEWAY.
  
 4. REMOVE THE EXFILTRATION TRENCH OUT OF THE RIGHT OF
 WAY.
  
 5. MOVE THE DRAINAGE CONTROL STRUCTURE (WEIR) OUT OF
 THE RIGHT OF WAY.
  
 6. ALL STORM PIPE WITHIN THE RIGHT OF WAY TO BE RCP,
 MINIMUM 15" IN DIAMETER.
  
 7. ON SECTION B-B ON PAGE C-9, IT APPEARS THERE IS A
 GRADE BREAK OF THE ROADWAY SURFACE NEAR THE VALLEY
 GUTTER. THE VALLEY GUTTER SHOULD BE LABELED AS 2'
 INSTEAD OF 1.50'.
  
 8. SHOW TYPE 'F' C&G FOR SECTION C-C INSTEAD OF
 EXISTING TYPE 'D'.
  
 9. SECTION D-D FOR THE 15.6' WIDE SIDEWALK ON S. DIXIE
 HWY SHOWS MAX. 2% CROSS SLOPE OR 3.75 INCHES OF
 VERTICAL FALL FROM BUILDING FACE TO BACK OF CURB. THE
 FFE OF 15.0 FT NAVD IS MORE THAN 2 FEET HIGHER THAN THE
 BACK OF CURB. HOW WILL THE SIDEWALK BE GRADED,
 PARTICULARLY AT THE DOORWAY ENTRANCE TO THE RETAIL AREA
 AT THE SOUTHEAST CORNER OF THE BUILDING? THE VERTICAL
 DIFFERENCE MAY NEED TO BE MADE UP INSIDE THE BUILDING
 INSTEAD OF RAISING THE SIDEWALK GRADES. IS THERE A
 WHEEL CHAIR RAMP FROM THE PUBLIC SIDEWALK TO THE
 LOUNGE?
  
 10. THERE ARE STEPS SHOWN AT THE SOUTH END OF THE
 BUILDING. WILL THE SIDEWALK MEET ADA SLOPE CRITERIA
 ADJACENT TO THE STEPS?
  
 11. IT APPEARS SURFACE RUNOFF ON GARDENIA STREET WILL
 FLOW WEST FROM THE EAST DRIVEWAY TO PROPOSED CB C-4.
 EXTEND THE TYPE 'F' C&G TO THE CATCH BASIN.
  
 12. THE VALVE BOX FOR THE FIRE HYDRANT SHALL NOT FALL
 WITHIN THE GUTTER.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT