Plan Review Notes
Plan Review Notes For Project Z19100014
Project Number Z19100014
Review Stop ENG - PPRC
Sequence Number 3
Notes
Date Text
2021-03-04 08:39:54COMMENTS FROM RICK ROSSANO, PROJECT COORD, ENG SERVICES
 ? 561-494-1098, [email protected]
  
 PLEASE RECHECK AS-BUILTS AND CONFIRM CORRECT SIZE AND
 MATERIAL OF EXISTING SANITARY LINE IN ALLEY WHERE
 SANITARY TAP IS PROPOSED.
  
 PLEASE UPDATE ALL CITY OF WPB STANDARD DETAILS TO MOST
 CURRENT VERSIONS. CONTACT [email protected] FOR ASBUILTS
 AND CURRENT CAD FILES OF CITY OF WPB STANDARD DETAILS &
 NOTES.
  
 PLEASE PROVIDE ELEVATION CONVERSION NOTE ON ALL UTILITY
 AND PAVING SHEETS.
  
 PLEASE INCLUDE FIRE AND IRRIGATION IF ANY IN WATER
 DEMAND TABLE ON UTILITY SHEET.
  
 THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES,
 PLEASE CONTACT 561-494-2262 OR [email protected]:
  
 -PLEASE VERIFY DOMESTIC METER AND BACKFLOW ASSEMBLY ARE
 OUTSIDE OF BUILDING.
  
 -UTILITY PLAN SAYS IRRIGATION METER IS 0.5INCH. WPB
 UTILITIES DOES NOT OFFER A 0.5INCH IRRIGATION METER.
  
 -FOR FORMAL ENGINEERING SUBMITTAL: LABEL IRRIGATION
 WATER SERVICE PIPE SIZE AND MATERIAL TYPE, UPDATE WATER
 SERVICE STANDARD DETAILS TO NEWEST REVISION, SHOW WATER
 SERVICE TAPS FOR NORTH SIDE OF GARDENIA ON UTILITY
 PLAN.
  
 -PROPERTY OWNER WILL BE REQUIRED TO SUBMIT AND RECORD A
 BACKFLOW COVENANT.
  
 -CANNOT FIND REMOVAL OF THE EXISTING WATER SERVICES AND
 METER BOXES ON GARDENIA AND DIXIE ON DEMO OR UTILITY
 PLANS. PLEASE ADD.
  
 -THE SIZE OF THE DOMESTIC AND IRRIGATION METER COMBINED
 IS LARGER THAN THE TAP. PLEASE VERIFY BUILDING WILL
 HAVE SUFFICIENT WATER IF IRRIGATION IS RUNNING.
  
 -THERE IS AN EXISTING TRAFFIC SIGNAL BOX AT THE EAST
 SIDE OF THE ALLEY THAT LOOKS TO BE CONFLICTING WITH THE
 CURB AND SIDEWALK. PLEASE RESOLVE.
  