Plan Review Notes
Plan Review Notes For Project Z19090032
Project Number Z19090032
Review Stop ENG - PPRC
Sequence Number 2
Notes
Date Text
2021-07-01 08:33:59PERVIOUS/IMPERVIOUS CALCULATIONS TO BE SHOWN ON
 ENGINEERING PLANS.
 PLEASE SHOW WATER (INCL. FIRE AND IRRIGATION) AND
 SANITARY DEMANDS TO SHEET 4 OF SITE PLAN SUBMITTAL.
 PLEASE ADD INLET PROTECTION (FILTER FABRIC) TO ALL
 NEARBY DRAINAGE STRUCTURES.
 PLEASE CONFIRM ALL CITY OF WPB STANDARD DETAILS ARE
 MOST CURRENT VERSIONS. CONTACT JANICE TARBILL AT
 [email protected] FOR CAD FORMAT VERSION.
 PLEASE PROVIDE CCTV OF EXISTING SANITARY PIPE ON 19TH
 ST. LABEL EXISTING PIPE MATERIAL AND SIZE.
 PLEASE SHOW PAVEMENT RESTORATION (50 FT. EACH SIDE OF
 TAP) AT SCALE PER CIT OF WPB STANDARD DETAIL GC-8.
  
  
 COMMENTS PER MARK HURLEY FIELD CUSTOMER SERVICE
 SUPERVISOR, CITY OF WEST PALM BEACH PUBLIC UTILITIES
 561-822-2262 [email protected]
  
 -ON WATER AND DEMO PLANS, SHOW ALL EXISTING AND
 PROPOSED UTILITY INFRASTRUCTURE. APPEARS LARGE SEWER
 MAIN ALONG WEST SIDE OF PROPERTY IS MISSING AS WELL AS
 SEWER LATERAL ON NORTH SIDE OF PROPERTY FOR THE
 EXISTING BUILDING.
  
 -SHOW AND LABEL EXISTING DOMESTIC METER AND BACKFLOW
 ASSEMBLY ON NORTH SIDE OF PROPERTY WEST OF WEST
 DRIVEWAY.
  
 -FOR FORMAL ENGINEERING SUBMITTAL: 1) PROVIDE SEPARATE
 BLOWUP DETAIL OF AREA AROUND DCDA. 2) LABEL ALL
 PROPOSED PIPE WITH SIZE AND MATERIAL TYPE. 3) ADD INV
 ELEVATION INFO TO LABELS OF SANITARY MANHOLES ON 19TH
 ST. 4) LABEL ALL EXISTING WATER AND SEWER MAINS WITH
 PIPE SIZE AND MATERIAL TYPE. 5) ADD GATE VALVE UPSTREAM
 OF DCDA BEFORE METER TAP SO FIRELINE CAN BE SHUT OFF
 WITHOUT AFFECTING THE OTHER WATER METER. 6) ADD SIZE OF
 PROPOSED BACKFLOW ASSEMBLIES TO LABELS. 7) LABEL
 EXISTING WATER SERVICES WITH PIPE SIZE AND MATERIAL
 TYPE. 8) SHOW ALL EXISTING WATER MAIN VALVES IN
 STREETS.
  
 -SANITARY MANHOLE APPEARS TO BE MISSING FROM WATER PLAN
 NEAR NW AREA OF PROPERTY. PLEASE ADD.
  
 -SEWER LATERAL SHOWS ALL WASTEWATER FLOWING THROUGH
 GREASE TRAP. IS THAT CORRECT?
  
 -VERIFY WHAT EXISTING WATER PIPE AT PROPOSED LOCATION
 OF GYMNASIUM FEEDS. ALSO ADD LABEL DESCRIBING WHAT IS
 HAPPENING TO IT ON WATER AND DEMO PLANS.
  
 -LABEL THE EXISTING IRRIGATION WATER SERVICE.
  
 -ADD WATER DEMAND CALCULATIONS TO WATER PLAN.
  
 -WILL THE FIRELINE JUST FEED THE NEW BUILDING OR ALSO
 THE EXISTING BUILDING?
  
 -REVIEW ANY PROPOSED TREES ON SIDES OF PROPERTY TO
 ENSURE NO CONFLICTS WITH EXISTING AND PROPOSED WATER
 SERVICES AND SEWER LATERALS. INCREASE CLEARANCE
 DISTANCES AND ADD ROOT BARRIERS AS NEEDED.
  
 -SHOW AND LABEL FIRE HYDRANT NEAR NE AREA OF PROPERTY.
  