| 2021-07-01 08:33:59 | PERVIOUS/IMPERVIOUS CALCULATIONS TO BE SHOWN ON |
| | ENGINEERING PLANS. |
| | PLEASE SHOW WATER (INCL. FIRE AND IRRIGATION) AND |
| | SANITARY DEMANDS TO SHEET 4 OF SITE PLAN SUBMITTAL. |
| | PLEASE ADD INLET PROTECTION (FILTER FABRIC) TO ALL |
| | NEARBY DRAINAGE STRUCTURES. |
| | PLEASE CONFIRM ALL CITY OF WPB STANDARD DETAILS ARE |
| | MOST CURRENT VERSIONS. CONTACT JANICE TARBILL AT |
| | [email protected] FOR CAD FORMAT VERSION. |
| | PLEASE PROVIDE CCTV OF EXISTING SANITARY PIPE ON 19TH |
| | ST. LABEL EXISTING PIPE MATERIAL AND SIZE. |
| | PLEASE SHOW PAVEMENT RESTORATION (50 FT. EACH SIDE OF |
| | TAP) AT SCALE PER CIT OF WPB STANDARD DETAIL GC-8. |
| | |
| | |
| | COMMENTS PER MARK HURLEY FIELD CUSTOMER SERVICE |
| | SUPERVISOR, CITY OF WEST PALM BEACH PUBLIC UTILITIES |
| | 561-822-2262 [email protected] |
| | |
| | -ON WATER AND DEMO PLANS, SHOW ALL EXISTING AND |
| | PROPOSED UTILITY INFRASTRUCTURE. APPEARS LARGE SEWER |
| | MAIN ALONG WEST SIDE OF PROPERTY IS MISSING AS WELL AS |
| | SEWER LATERAL ON NORTH SIDE OF PROPERTY FOR THE |
| | EXISTING BUILDING. |
| | |
| | -SHOW AND LABEL EXISTING DOMESTIC METER AND BACKFLOW |
| | ASSEMBLY ON NORTH SIDE OF PROPERTY WEST OF WEST |
| | DRIVEWAY. |
| | |
| | -FOR FORMAL ENGINEERING SUBMITTAL: 1) PROVIDE SEPARATE |
| | BLOWUP DETAIL OF AREA AROUND DCDA. 2) LABEL ALL |
| | PROPOSED PIPE WITH SIZE AND MATERIAL TYPE. 3) ADD INV |
| | ELEVATION INFO TO LABELS OF SANITARY MANHOLES ON 19TH |
| | ST. 4) LABEL ALL EXISTING WATER AND SEWER MAINS WITH |
| | PIPE SIZE AND MATERIAL TYPE. 5) ADD GATE VALVE UPSTREAM |
| | OF DCDA BEFORE METER TAP SO FIRELINE CAN BE SHUT OFF |
| | WITHOUT AFFECTING THE OTHER WATER METER. 6) ADD SIZE OF |
| | PROPOSED BACKFLOW ASSEMBLIES TO LABELS. 7) LABEL |
| | EXISTING WATER SERVICES WITH PIPE SIZE AND MATERIAL |
| | TYPE. 8) SHOW ALL EXISTING WATER MAIN VALVES IN |
| | STREETS. |
| | |
| | -SANITARY MANHOLE APPEARS TO BE MISSING FROM WATER PLAN |
| | NEAR NW AREA OF PROPERTY. PLEASE ADD. |
| | |
| | -SEWER LATERAL SHOWS ALL WASTEWATER FLOWING THROUGH |
| | GREASE TRAP. IS THAT CORRECT? |
| | |
| | -VERIFY WHAT EXISTING WATER PIPE AT PROPOSED LOCATION |
| | OF GYMNASIUM FEEDS. ALSO ADD LABEL DESCRIBING WHAT IS |
| | HAPPENING TO IT ON WATER AND DEMO PLANS. |
| | |
| | -LABEL THE EXISTING IRRIGATION WATER SERVICE. |
| | |
| | -ADD WATER DEMAND CALCULATIONS TO WATER PLAN. |
| | |
| | -WILL THE FIRELINE JUST FEED THE NEW BUILDING OR ALSO |
| | THE EXISTING BUILDING? |
| | |
| | -REVIEW ANY PROPOSED TREES ON SIDES OF PROPERTY TO |
| | ENSURE NO CONFLICTS WITH EXISTING AND PROPOSED WATER |
| | SERVICES AND SEWER LATERALS. INCREASE CLEARANCE |
| | DISTANCES AND ADD ROOT BARRIERS AS NEEDED. |
| | |
| | -SHOW AND LABEL FIRE HYDRANT NEAR NE AREA OF PROPERTY. |
| | |
| |