| 2019-10-09 19:55:49 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. |
| | |
| | 2. FLOOD ZONE. ACCORDING TO THE ADOPTED FLOOD INSURANCE |
| | RATE MAPS (FIRMS), THE PROPOSED BUILDING IS IN FLOOD |
| | ZONE AE, WITH A BASE FLOOD ELEVATION OF 14 FT NAVD. THE |
| | FIRST FLOOR OF THE BUILDING AND ALL ASSOCIATED |
| | MECHANICAL EQUIPMENT (CHILLERS, GENERATORS ETC.) SHALL |
| | BE AT OR ABOVE 16 FT NAVD SO THAT THEY ARE THE REQUIRED |
| | 24 INCHES (FREEBOARD) ABOVE THE BASE FLOOD ELEVATION. |
| | |
| | 3. UNITY OF TITLE. FOR ANY BUILDING CROSSING A PROPERTY |
| | LINE, EITHER A RECORDED UNITY OF TITLE, OR SOME OTHER |
| | APPROVED LEGAL INSTRUMENT, SHALL BE INCLUDED WITH THE |
| | PERMIT APPLICATION, OR THE BUILDING MUST HAVE A FIRE |
| | WALL ALONG THE PROPERTY LINE, PER SECTION 202 OF |
| | FLORIDA BUILDING CODE, BUILDING, FIRE SEPARATION |
| | DISTANCE. |
| | |
| | 4. ACCESSIBLE ROUTE. WHEN SUBMITTED FOR PERMIT, THE |
| | PLANS SHALL SHOW AT LEAST ONE ACCESSIBLE ROUTE, |
| | COMPLYING WITH SECTIONS 206.2 AND 402.2 OF FLORIDA |
| | ACCESSIBILITY CODE, CONNECTING ACCESSIBLE BUILDING OR |
| | FACILITY ENTRANCES WITH ALL ACCESSIBLE SPACES AND |
| | ELEMENTS WITHIN THE BUILDING OR FACILITY |
| | |
| | 5. NUMBER OF ACCESSIBLE PARKING SPACES. OVERALL SITE |
| | PLAN, SHEET OSP, STATES THAT 9 ACCESSIBLE PARKING |
| | SPACES ARE PROVIDED BUT THE PLANS APPEAR TO SHOW ONLY |
| | 8. ALSO 2% OF THE NUMBER OF PROVIDED PARKING SPACES |
| | SHALL BE ACCESSIBLE, SO 11 ACCESSIBLE PARKING SPACES |
| | ARE REQUIRED BECAUSE A TOTAL OF 509 PARKING SPACES ARE |
| | PROPOSED. THE MINIMUM NUMBER OF ACCESSIBLE PARKING |
| | SPACES PROVIDED SHALL BE IN ACCORDANCE WITH FAIR |
| | HOUSING ACT AND SECTION 208.2 OF FLORIDA ACCESSIBILITY |
| | CODE. |
| | |
| | 6. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, |
| | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR |
| | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, |
| | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE |
| | FLORIDA BUILDING CODE. |
| | |
| | 7. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, |
| | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND |
| | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, |
| | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. |
| | |
| | 8. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT |
| | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL |
| | HAVE A SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT |
| | MICHAEL ORIO, GIS SUPPORT SPECIALIST, AT (561) 494 |
| | 1080, OR BY EMAIL: [email protected] |
| | |
| | 9. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT |
| | TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE |
| | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP |
| | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC |
| | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: |
| | [email protected] |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |