Plan Review Notes
Plan Review Notes For Project Z19090009
Project Number Z19090009
Review Stop Z
Sequence Number 2
Notes
Date Text
2020-01-08 08:38:23CASE NO. PB1248GG - 1ST RESUBMITTAL REVIEW
 MORSELIFE AUDITORIUM & GENERATOR
 4920 LORING DRIVE
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FIVE
 (5) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE COMMENTS WITHIN 60 DAYS FROM
 THE DATE OF THE COMMENTS (BY MARCH, 7, 2020), THE CASE
 SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL
 REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 ADDITIONAL RESUBMITTAL AT NO ADDITIONAL COST. IF
 PREVIOUSLY-ISSUED COMMENTS CONTINUE TO NOT BE
 SUFFICIENTLY ADDRESSED, THE APPLICANT WILL BE ASSESSED
 A RESUBMITTAL FEE. SUCH FEE WILL BE 20% OF THE ORIGINAL
 APPLICATION FEE ($60).
  
 GENERATOR
  
 1) UPDATED COMMENT: THE MASTER PLAN PROVIDES THE
 GENERATOR ENCLOSURE DIMENSION AS 24 FEET X 50 FEET, YET
 NONE OF THE PLANS SHOW THE GENERATOR ENCLOSURE AS THAT
 LARGE. THE PLANS SEEM TO SHOW THE SAME SIZED GENERATOR
 ALL IN THE SAME LOCATION, BUT STAFF IS UNABLE TO VERIFY
 DUE TO THE CONFLICTING INFORMATION. THE PLANS NEED TO
 CLEARLY SHOW GENERATOR ENCLOSURE DIMENSIONS
  
 2) REPEAT COMMENT: THE PLANS NEED TO INDICATE THE 12
 FOOT TALL GENERATOR WALLS AND WHERE THE GATE OPENINGS
 ARE. NO DETAIL OF THE GENERATOR ENCLOSURE, INCLUDING
 THE GENERATOR AND THE WALLS, WAS PROVIDED.
  
 3) REPEAT COMMENT: THE PLANS NEED TO SHOW THE DIMENSION
 OF THE GENERATOR WALL FROM THE END OF THE PARKING
 SPACES AND DRIVE AISLE CURB LINE. THIS NEEDS TO BE A
 MINIMUM OF FIVE (5) FEET TO INCLUDE THE LANDSCAPE
 SCREENING LISTED IN THE JUSTIFICATION LETTER. PLEASE
 REMEMBER THAT THE PARKING SPACES ALONG RYNA GREENBAUN
 DRIVE WERE CONSTRUCTED WITH THE TWO (2) FOOT OVERHANG,
 SO THIS OFF SET NEEDS TO BE INCLUDED SEVEN (7) FEET
 TOTAL. NO DIMENSIONS SHOWN ON THE PLANS.
  
 4) UPDATED COMMENT: THE PROPOSED GENERATOR IS
 STRADDLING THE PROPERTY LINE BETWEEN THE MORSELIFE SITE
 AND THE FORMER HOMESAFE SITE. THIS WILL NEED TO BE
 ADDRESSED AS A SPECIFIC DEVELOPMENT REGULATION
 ALLOWANCE WITH THE FORTHCOMING MAJOR PLANNED
 DEVELOPMENT AMENDMENT FOR THE PACE RELOCATION AND
 HOSPICE CONSTRUCTION. STAFF NEEDS TO REVIEW THE
 GENERATOR ENCLOSURE DETAIL (COMMENT #2) TO DETERMINE
 HOW THIS WILL BE ADDRESSED WITH THE MAJOR PLANNED
 DEVELOPMENT.
  
 CONNECTION
  
 5) UPDATED COMMENT: NO LANDSCAPE PLAN SHOWING THE AREA
 AROUND THE CONNECTION WAS PROVIDED. THE LANDSCAPE ON
 THE NORTHERN PARCEL IS NOT SHOWN.
  
 GENERAL
  
 6) REPEAT COMMENT: WHERE IS THE "HOMESAFE OFFICE"
 REFERRED TO ON THE MASTER SITE DATA TABLE? THIS 6,111
 SQUARE FOOT BUILDING DOES NOT APPEAR ON THE MASTER
 PLAN. THE 12,200 SQUARE FEET ON THE NORTH PARCEL
 INCLUDE THE THREE BUILDINGS WHICH CURRENTLY EXIST. THIS
 WAS NOT REMOVED FROM THE MASTER SITE DATA TABLE (AND IS
 STILL SHOWN ON THE HOSPICE/PACE EXPANSION MAJOR
 AMENDMENT MASTER SITE DATA TABLE).
  
 7) REPEAT COMMENT: THE HOUSING BREAKDOWN TABLE HAS
 ADDED 10 BEDS UNDER THE TRADITION PHASE II RESIDENTIAL
 LINE ITEM WHICH PREVIOUSLY DID NOT EXIST. THESE HOSPICE
 BEDS WERE NOT REMOVED FROM THE HOUSING BREAKDOWN TABLE.
  