Plan Review Notes
Plan Review Notes For Project Z19090009
Project Number Z19090009
Review Stop Z
Sequence Number 1
Notes
Date Text
2019-10-09 14:38:41CASE NO. PB1248GG
 MORSELIFE AUDITORIUM & GENERATOR
 4920 LORING DRIVE
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FIVE
 (5) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THE PPRC MEETING (BY DECEMBER 10,
 2019), THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY
 FURTHER ACTION SHALL REQUIRE A NEW DEVELOPMENT
 APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($60).
  
 1) THE CHECK SUBMITTED WITH THE ORIGINAL APPLICATION
 DID NOT COVER THE FULL FEES FOR THE APPLICATION. YOU
 STILL OWE THE CITY $1,288. PLEASE SEE THE PREVIOUS
 E-MAIL TO ALEX AHRENHOLZ FOR THE BACK UP ON THE FEE
 CALCULATION.
  
 AUDITORIUM
  
 2) IT APPEARS THERE ARE TWO WALKWAYS LEADING TO THE
 SIDEWALK ON THE EAST SIDE OF THE PROPOSED AUDITORIUM
 THAT ARE NOT SHOWN ON THE CIVIL PLAN.
  
 3) PROVIDE VERIFICATION FROM THE CITY'S BUILDING
 DIVISION THAT THE ENTRIES SHOWN ON THE EAST SIDE OF THE
 AUDITORIUM DO NOT REQUIRE THE ADDITION OF ADA PARKING
 SPACES.
  
 GENERATOR
  
 4) THE PLANS NEED TO INCLUDE THE GENERATOR ENCLOSURE
 DIMENSIONS. IT IS UNCLEAR FROM THE PROVIDED PLANS IF
 THE GENERATOR "BOX" IS THE PAD OR THE ENCLOSURE WALLS.
  
 5) THE PLANS NEED TO INDICATE THE 12 FOOT TALL
 GENERATOR WALLS AND WHERE THE GATE OPENINGS ARE.
  
 6) THE PLANS NEED TO SHOW THE DIMENSION OF THE
 GENERATOR WALL FROM THE END OF THE PARKING SPACES AND
 DRIVE AISLE CURB LINE. THIS NEEDS TO BE A MINIMUM OF
 FIVE (5) FEET TO INCLUDE THE LANDSCAPE SCREENING LISTED
 IN THE JUSTIFICATION LETTER. PLEASE REMEMBER THAT THE
 PARKING SPACES ALONG RYNA GREENBAUN DRIVE WERE
 CONSTRUCTED WITH THE TWO (2) FOOT OVERHANG, SO THIS OFF
 SET NEEDS TO BE INCLUDED. THE LANDSCAPE PLAN APPEARS TO
 ONLY HAVE A FOUR (4) FOOT PLANTING AREA DUE TO THE
 PROXIMITY TO THE OVERHANG.
  
 7) IT APPEARS THAT THE GENERATOR "BOX" IS SHOWN
 DIFFERENTLY (SIZE AND SETBACKS) ON THE MASTER PLAN,
 LANDSCAPE PLAN AND THE CIVIL PLAN. IT CLEARLY AVOIDS
 THE 12 FOOT UTILITY EASEMENT ON THE CIVIL PLAN, BUT
 SINCE THIS EASEMENT IS NOT SHOWN ON THE MASTER PLAN OR
 THE LANDSCAPE PLAN, STAFF IS UNABLE TO TELL IF THE
 GENERATOR ENCLOSURE IS LOCATED OUTSIDE OF THE EASEMENT.
  
 8) THE LANDSCAPE SCREEN HEDGE IS NOT PROVIDED ON THE
 NORTH SIDE OF THE GENERATOR ENCLOSURE.
  
 9) THE RELOCATED FENCE IS NOT SHOWN ON THE LANDSCAPE
 PLAN OR THE MASTER PLAN.
  
 10) THE PROPOSED GENERATOR IS STRADDLING THE PROPERTY
 LINE BETWEEN THE MORSELIFE SITE AND THE FORMER HOMESAFE
 SITE. THIS WILL NEED TO BE ADDRESSED AS A SPECIFIC
 DEVELOPMENT REGULATION ALLOWANCE WITH THE FORTHCOMING
 MAJOR PLANNED DEVELOPMENT AMENDMENT FOR THE PACE
 RELOCATION AND HOSPICE CONSTRUCTION.
  
 CONNECTION
  
 11) A PEDESTRIAN ROUTE, SEPARATED FROM THE VEHICULAR
 TRAVEL LANES, NEEDS TO BE INCLUDED WITH THE VEHICULAR
 CONNECTION BETWEEN THE TWO SITES. THE PEDESTRIAN ROUTE
 NEEDS TO CONNECT THE SIDEWALK NETWORK ON THE MORSELIFE
 SITE WITH THE SIDEWALK NETWORK ON THE FORMER HOMESAFE
 SITE.
  
 12) THE RESUBMITTED MASTER PLAN AND CIVIL PLAN NEED TO
 SHOW THE FINAL CONNECTION LAYOUT WITHOUT THE EXISTING
 CURBS, PARKING SPACES, ETC., SINCE THIS WILL BE THE
 APPROVED LAYOUT.
  
 13) PLEASE CLARIFY IF THE DIVIDER MEDIAN IN THE DRIVE
 AISLE BY THE NEW VEHICULAR CONNECTION IS BEING REMOVED.
 THE LINE WORK ON THE CIVIL PLAN SEEMS TO INDICATE THIS,
 BUT IT IS NOT NOTED ON THE PLAN.
  
 14) NO LANDSCAPE PLAN SHOWING THE AREA AROUND THE
 CONNECTION WAS PROVIDED.
  
 15) SHOW THE PROPOSED GATE DETAILS AT THE CONNECTION.
  
 GENERAL
  
 16) WHERE IS THE "HOMESAFE OFFICE" REFERRED TO ON THE
 MASTER SITE DATA TABLE? THIS 6,111 SQUARE FOOT BUILDING
 DOES NOT APPEAR ON THE MASTER PLAN. THE 12,200 SQUARE
 FEET ON THE NORTH PARCEL INCLUDE THE THREE BUILDINGS
 WHICH CURRENTLY EXIST.
  
 17) THE HOUSING BREAKDOWN TABLE HAS ADDED 10 BEDS UNDER
 THE TRADITION PHASE II RESIDENTIAL LINE ITEM WHICH
 PREVIOUSLY DID NOT EXIST. WHAT ARE THESE? IF BEDS HAVE
 BEEN ADDED AT THE EXPENSE OF UNITS, THEN THE UNIT COUNT
 NEEDS TO BE REDUCED ACCORDINGLY. NOTE: THERE ARE ONLY 4
 UNITS AVAILABLE TO CONVERT TO BEDS IN THE PROJECT IF
 THE NUMBER OF UNITS IN TRADITIONS PHASE II REMAINS AT
 182.
  