Plan Review Notes
Plan Review Notes For Project Z19090006
Project Number Z19090006
Review Stop STORM
Sequence Number 2
Notes
Date Text
2020-01-30 19:57:46THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 1/27/2020 SUBMITTAL PACKAGE AND THE COMMENTS CAN BE
 ADDRESSED DURING ENGINEERING PERMIT APPLICATION:
  
 1. THERE IS AN EXISTING DRAINAGE SYSTEM THAT APPEARS TO
 HAVE TWO CONTROL STRUCTURES - WEIR IN THE CATCH BASIN
 AT NORTHEAST CORNER OF THE SITE AND WEIR IN THE CATCH
 BASIN ALONG THE WEST PROPERTY LINE, SOUTH OF THE
 PROPOSED DUMPSTER LOCATION. THE WESTERN CONTROL
 STRUCTURE WILL PREVENT STORMWATER RUNOFF FROM THE TWO
 NORTHERN EXISTING CATCH BASINS FROM REACHING THE
 EXFILTRATION TRENCH. ADVISE IF THE WESTERN CONTROL
 STRUCTURE IS NEEDED.
  
 2. THIS EXISTING SYSTEM IS CONNECTED TO THE BELVEDERE
 ROAD DRAINAGE SYSTEM. THIS ROADWAY DRAINAGE SYSTEM IS
 EITHER MAINTAINED BY FDOT OR PALM BEACH COUNTY. OBTAIN
 ACKNOWLEDGEMENT FROM THE APPROPRIATE ENTITY TO CONTINUE
 THIS DRAINAGE CONNECTION.
  
 3. PROVIDE ADDITIONAL PROPOSED GRADES IN THE DRIVEWAY
 PAVER AREA ALONG THE NORTH SIDE OF THE SITE SHOWING THE
 CENTER OF THE PAVER AREA IS LOWER THAN THE EDGE OF
 PAVEMENT ALONG THE OUTER CURB AND THAT RUNOFF WILL NOT
 FLOW FROM THE DRIVEWAY AREA TO THE SIDEWALK OPENINGS ON
 THE NORTH PROPERTY LINE.
  
 4. PROVIDE DETAILS OF THE PERVIOUS PAVER DESIGN.
  
 5. STAFF SUGGESTS ADDING BAFFLES IN CB#1 QND CB#2 TO
 EXTEND THE LIFE OF THE EXFILTRATION TRENCH. THESE
 STRUCTURES MAY NOT SEE MUCH SURFACE RUNOFF DUE TO BEING
 LOCATED WITHIHN THE PERVIOUS PAVER AREA BUT THE BAFFLES
 WILL KEEP SOME FLOATABLES AND SEDIMENT OUT OF THE
 EXFILTRATION TRENCH.
  
 TRACY WARD, P.E.
 SENIOR STORMWWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120