Notes
Date Text
2020-01-06 11:56:09COMMENTS PER MARK HURLEY, CUSTOMER SERVICE SUPERVISOR,
 PUBLIC UTILITIES, 561-822-2262, [email protected]
  
 -MORE VERIFICATION NEEDS TO BE DONE ON THE EXISTING
 WATER SERVICES AND PLANS UPDATED WITH FINDINGS. FOR
 EXAMPLE, SITE VISIT FOUND THAT DCDA FIRELINE BACKFLOW
 IS 8 INCH AND THAT THERE IS A 1.5 INCH ACTIVE
 IRRIGATION METER IN THE SIDEWALK. THE EXISTING METER IN
 THE SIDEWALK IS NOT A FIRE METER ? IT IS A 3 INCH
 DOMESTIC METER (NOT SEEING A 6 INCH FIRE METER IN
 SIDEWALK). THE WATER LINES NEAR THE PROPERTY/ROW LINE
 ON THE PLAN, DO NOT MATCH OUR GIS AND SKETCH DRAWINGS ?
 CARE SHOULD BE TAKEN TO LOCATE AND VERIFY WHERE THE
 EXISTING PIPING IS SPECIFICALLY LOCATED AND HOW IT IS
 SETUP, AND THEN HAVE PLAN REFLECT THAT.
  
 -THE SIZE/FOOTPRINT OF THE EXISTING WATER METER VAULT
 IN SIDEWALK NEAR SE CORNER OF PROPERTY DOES NOT LOOK
 ACCURATELY REPRESENTED ON PLAN.
  
 -TAP OF PROPOSED 1 INCH WATER SERVICE MAY NEED BE
 RELOCATED SLIGHTLY WEST OR NORTH GIVEN THE EXISTING 1.5
 INCH METER TAP NOT SHOWN AND THE PROXIMITY TO DRIVEWAY
 (DO NOT WANT TAP IN DRIVEWAY ? CURRENT DRIVEWAY HAS
 ANGLES, BUT THOSE ARE NOT SHOWN ON PLAN).
  
 -PLAN DRAWING DOES NOT REFLECT EXISTING TWIN/PARALLEL 4
 INCH RPPA?S (1 MISSING). ALSO MISSING ONE SMALLER
 EXISTING BACKFLOW ASSEMBLY FOR IRRIGATION.
  
 -PLAN NOT SHOWING OTHER UTILITIES LIKE GAS OR
 COMMUNICATION NEAR SE CORNER OF PROPERTY. IS THAT
 BECAUSE THERE ARE NONE, OR WERE THEY JUST NOT ADDED? IF
 THERE ARE OTHER UNDERGROUND UTILITIES WHICH COULD
 CONFLICT WITH THE WATER LINE INSTALLATION, SHOULD BE
 SHOWN ON PLAN.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR WPB, FL 33401 (MAILING
 ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098
 FAX: (561) 494-1116 MOBILE: (561) 246-9525
 EMAIL: [email protected] WWW.WPB.ORG/ENGINEERING
  
  
  Print


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved