| 2019-10-03 14:13:38 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, |
| | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM |
| | BEACH FIRE RESCUE. |
| | |
| | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE |
| | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. |
| | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS |
| | ARE SUBMITTED FOR PERMIT. |
| | |
| | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE |
| | PROPOSED PROJECT. |
| | |
| | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE |
| | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A |
| | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED |
| | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN |
| | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY |
| | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER |
| | PROTECTION. |
| | |
| | 2. SITE ACCESS(DURING CONSTRUCTION) AND EXIT POINTS ARE |
| | TO BE CLEARLY IDENTIFIED AND MAINTAINED FOR EMERGENCY |
| | VEHICLES DURING ALL CONSTRUCTION ACTIVITIES. |
| | |
| | PROPOSED SITE ACCESS(FINSIHED SITE) AND TRAVEL PATHS |
| | ARE ACCEPTABLE. |
| | |
| | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM |
| | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. |
| | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND |
| | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT |
| | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. |
| | |
| | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE |
| | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE |
| | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. |
| | |
| | 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH |
| | THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, |
| | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. |
| | |
| | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE |
| | OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | 7. FOR PLAN REVIEW SUBMITTAL, ALL EXISTING AND NEW FIRE |
| | HYDRANTS PLANNED FOR THIS DEVELOPMENT SHALL BE CLEARLY |
| | INDICATED AND IDENTIFIED ON THE PLAN AND CLOSELY |
| | COORDINATED WITH THE BUREAU OF FIRE PREVENTION. |
| | |
| | THERE IS AN EXISITNG FIRE HYDRANT LOCATED ON THE SITE |
| | PLAN THAT IS ACCEPTABLE. NO ADDITIONAL NOR NEW FIRE |
| | HYDRANTS ARE REQUIRED. HOWEVER, IT IS UNKNOWN IF THIS |
| | IS A PRIVATE HYDRANT OR CITY OWNED. IF PRIVATE, A |
| | FLOW/GPM TEST AND NEEDED MAINTENANCE IS REQUIRED OR |
| | ENSURED. |
| | |
| | 8. FOR PLAN REVIEW SUBMITTAL, COMPLETE LIFE SAFETY |
| | PLANS FOR EACH OCCUPANCY SHALL BE PROVIDED THAT |
| | ILLUSTRATE OCCUPANT LOADS, TRAVEL DISTANCES, COMMON |
| | PATHS OF TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, |
| | EMERGENCY LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE |
| | EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES |
| | AND EQUIPMENT. |
| | |
| | 9. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES |
| | NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL. |
| | |
| | 10. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING |
| | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH |
| | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| |